Honeywell International Inc. 8DL5821-1 Manuale Utente

Pagina di 4
ÊK9947V3ÈŠ 
K9947V3    5/08  Rev. A 
SPECIFICATIONS 
Power:  3V lithium battery 
(Duracell DL123A, Panasonic CR123A)   
CAUTION:    Risk  of  fire,  explosion,  and  burns.    Do  not 
recharge, disassemble, heat above 212
°F 
(100
°C) or incinerate.  Dispose of used batteries 
promptly.  Keep away from children.   
Operating Temperature: 14
°F (-10°C) to 104°F 
(+40
°C)   
Operating Voltage: 3.2VDC 
Dimensions:   
3.1” length, 1.6”wide, 1.0” 
depth 
Sensor Parameters:   
Cold Temperature  
(Freeze) Detector 
45
°F (7°C) 
Warm Temperature  
Detector 75
°F (24°C) 
Hot Temperature 
Detector 95
°F (35°C) 
Refrigerator Failure 
Detector 42
°F (6°C) 
Freezer Failure  
Detector 10
°F (-12°C) 
Hysteresis 
✝✝✝
 
3
°F (-16°C) 
Flood Sensor 
¼ inch of water covering 
the probe 
Response Time  
Tolerance 
✝✝✝✝
 +50%, 
-20% 
Temperature Measurement 
Accuracy (internal temp. sensor  
or external temp. probe) 
±3
°F (-16°C) 
 
✝✝✝   Hysteresis is the temperature difference between “fault” and 
“restore” points.
 
✝✝✝✝ The Response Time Tolerance is the time duration necessary 
for the device to respond to a “fault” or “restore” condition.  
This time does not take into account the time necessary for 
the probe and circuitry to equalize to the ambient 
temperature.  This feature prevents false alarms due to open 
doors and other transitory conditions. 
 
 
 
 
TO THE INSTALLER 
Regular maintenance and inspection (at least annually) by the 
installer and frequent testing by the user are vital to continuous 
satisfactory operation of any alarm system.   
The installer should assume the responsibility of developing and 
offering a regular maintenance program to the user as well as 
acquainting the user with the proper operation and limitations of 
the alarm system and its components parts.  Recommendations 
must be included for a specific program of frequent testing (at least 
weekly) to ensure the system’s proper operation at all times.   
 
 
FCC / IC STATEMENT 
This device complies with Part 15 of the FCC rules and RSS210 of 
Industry Canada.  Operation is subject to the following two 
conditions:  (1) This device may not cause harmful interference, and 
(2) this device must accept any interference received, including 
interference that may cause undesired operation.   
Unauthorized changes or modifications could void the user's 
authority to operate the equipment. 
 
 
REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE 
CONTROL PANEL WITH WHICH THIS DEVICE IS USED FOR 
WARRANTY INFORMATION AND LIMITATIONS OF THE 
ENTIRE ALARM SYSTEM.   
 
 
 
2 Corporate Center Drive, Suite 100 
P.O. Box 9040, Melville, NY  11747 
Copyright
 2008 Honeywell International Inc. 
www.honeywell.com/security