Table 1:  5821 Operating Mode Choices 
✝      When the 5821 is used with either external probe, an open-circuit or a short-circuit of the probe’s wiring results in an alarm on 
that loop, and a trouble condition on all other programmed loops. 
✝✝   Use a maximum wire length of 48 inches between the 5821 and the 470PB probe. 
 
Operating Mode
 
Dip 
Switch 
Setting
 
Loop
 
Faults when… 
Restores when… 
External  
Probe 
 
Cold Temp Sensing 
SW1=OFF 
SW2=OFF 
temperature drops below 
45
°F (7°C) for >10 minutes.   
temperature rises 48
°F (9°C) 
for >4 minutes.   
No external  
probe 
Hot Temp Sensing 
SW1=OFF 
SW2=OFF 
temperature rises above 
95
°F (35°C) for >10 minutes.  
temperature drops below 92
°F 
(33
°C) for > 4 minutes.   
No external  
probe 
Warm Temp 
Sensing 
SW1=ON 
SW2=OFF 
temperature rises above 
75
°F (24°C) for >10 minutes.  
temperature drops below 72
°F 
(22
°C) for > 4 minutes.   
No external  
probe 
Freezer Temp  
Monitoring 
SW1=OFF 
SW2=ON 
temperature rises above 
10
°F  
(-12
°C) for >30 minutes.   
temperature drops below 7
°F  
(-14
°C) for > 4 minutes.   
Use T280R  
external probe 
Refrig. Temp 
Monitoring 
SW1=ON 
SW2=ON 
temperature rises above 
42
°F (6°C) for >30 minutes.   
temperature drops below 39
°F 
(4
°C) for > 4 minutes.   
Use T280R  
external probe 
Flood Sensing 
SW1=OFF 
SW2=ON 
external probe tips are in 
contact with water for >3 
minutes.   
probe tips have not been in 
contact with water for > 3 
minutes.   
Use 470PB ext. 
probe shunted by 
2.2M
Ω resistor ✝✝ 
Cold Temp Sensing 
SW1=ON 
 
1=Cold 
 
temperature drops below 
45
°F (7°C) for >10 minutes. 
temperature rises 48
°F (9°C) 
for >4 minutes. 
Warm Temp 
Sensing 
SW2=OFF 2=Warm 
temperature rises above 
75
°F (24°C) for >10 minutes.    
temperature drops below 72
°F 
(22
°C) for > 4 minutes. 
 
No external probe 
Cold Temp Sensing 
SW1=OFF 
1=Cold 
temperature drops below 
45
°F (7°C) for >10 minutes. 
temperature rises 48
°F (9°C) 
for >4 minutes.   
Hot Temp Sensing 
SW2=OFF 
2=Hot 
temperature rises above 
95
°F (35°C) for >10 minutes.  
temperature drops below 92
°F 
(33
°C) for > 4 minutes.   
 
No external probe 
Cold Temp Sensing 
SW1=ON 
 
1=Cold 
temperature drops below 
45
°F (7°C) for >10 minutes. 
temperature rises 48
°F (9°C) 
for >4 minutes. 
Refrig. Temp 
Monitoring 
SW2=ON 
2=Refrig 
temperature rises above 
42
°F (6°C) for >30 minutes.   
temperature drops below 39
°F 
(4
°C) for > 4 minutes.     
 
Use T280R  
external probe 
Cold Temp Sensing 
SW1=OFF 1=Cold 
 
temperature drops below 
45
°F (7°C) for >10 minutes. 
temperature rises 48
°F (9°C) 
for >4 minutes. 
Freezer Temp 
Monitoring 
SW2=ON 
2=Freezer 
temperature rises above 
10
°F (-12°C) for >30 
minutes.   
temperature drops below 7
°F  
(-14
°C) for > 4 minutes.     
Use T280R  
external probe 
Cold Temp Sensing 
SW1=OFF 1=Cold 
 
temperature drops below 
45
°F (7°C) for >10 minutes. 
temperature rises 48
°F (9°C) 
for >4 minutes. 
Flood Sensing 
SW2=ON 
3=Flood 
external probe tips are in 
contact with water for >3 
minutes.   
probe tips have not been in 
contact with water for > 3 
minutes. 
Use 470PB  
ext. probe 
shunted by 
2.2M
Ω resistor ✝✝