AC C E L E N S   ( AC S )  C AN o p e n  
 
 
 
 
6 .     T r o u b l e sh o o t i n g  
 
• Power on – Inclinometer doesn’t respond 
 
Problem: 
 
If  the  bus  is  active,  then,  the  installed 
 
inclinometer  is  transmitting  a  false  node 
 
number.  If  the  bus  is  inactive,  then,  it    was 
 
connected with an incorrect baud rate. 
 
 
 Possible solution: 
Modus pre-operational 
Adressing the inclinometer via SDO 
Reset or power off 
Reprogram the Baud rate 
 
• Malfunction  of  the  position  value  during 
transmission 
 
Problem: 
 
During  the  transmission  of    the  position  value 
 
occasional  malfunctions  occur.  The  CAN  bus 
 
can be   temporabily in the bus off state also 
 
 
Possible solution: 
 
Please  check  if  the  last  bus  nodes  have  the 
 
terminal  resistor.  If  the  last  bus  node  is  an 
 
inclinometer  the  terminal  resistor  is  to  be 
 
added. 
 
• Too many ERROR-Frames 
 
Problem:  
 
The  bus  load  is  too  high  in  case  of  too  many 
 
error frames.  
 
 
Possible solution: 
 
Check  if  all  bus    nodes  have  the  same 
 
baudrate.  Even  if  one  node  has  a  different 
 
baudrate, error   frames 
are 
produced 
 
automatically.  
• Unexpected  module  /  Module  missing  /  
Wrong Module 
 
Problem: 
 
Improper  definition  of  node  address  or 
 
improper loading of EDS file. 
 
 
Solution: 
 
Reinitialize  the  CAN  bus or  re-install the EDS 
 
file. 
 
• Node  state  stopped  upon  loading  and 
initialization 
 
Problem: 
 
Mostly  because  the  bus  transmission  timeout  
 
is  defined  lesser  than  the  ACS  transmission 
 
time. 
 
 
Solution: 
 
Increase 
the 
bus 
timeout 
 
period 
 
Approximately 2-3 seconds). 
 
• Unable to change to another node number
 
 
If  all  nodes  are  found  to  be  in  operational 
mode,  then  follow  the  next    few  steps  to  set 
the required  node  number  to  a  selected 
device. 
 
1.  Calculate  the  required  node  number  in 
hexadecimal. 
ACS 
is 
internally 
programmed to add 1 to any node number 
change fed to it, in order to avoid the node 
number 0)