Laser beta lasermike LS8000-3 Manuale Utente

Pagina di 221
LaserSpeed 8000-3 Instruction Handbook
 
Interfacing with the LS8000-3 
 
 
Part No. 93463 / Drawing No. 0921-01561 
Page 73 of 221 
Revision A (Sep 2007) 
 
Thermostat Interface 
In order to extend the ambient temperature range of LaserSpeed gauges, you 
can provide water or air cooling/heating.  This is often accomplished by 
connecting the gauge to a recirculating heater/chiller, but can also be 
accomplished by using the gauge's thermostat output.  LaserSpeed gauges 
monitor their internal temperatures, and can provide an output indicating when 
cooling/heating is required.  This output can be connected to a valve or a PLC 
in order to control the flow of coolant.  The thermostat output is available as an 
alternate configuration of the Index Pulse, the High Speed Pulse Output 
(Phase B), and the User Scaleable Pulse Output (Phase B.) 
 
Output 
How To Configure 
Output Pin 
Voltage Level 
Index Pulse 
Set Index Pulse Output Function to 
Thermostat Output
 
DB25/DB37 pin 22
 
5-24V, depending on 
User Input Voltage 
High Speed 
Pulse 
Set High Speed Pulse Output 
Configuration to either: 
System Ready/Thermostat Output or 
Valid/Thermostat Output 
DB25/DB37 pin 7 
DB25/DB37 pin 9 
RS-422 Output 
(2V-5V Differential) 
User 
Scaleable 
Pulse 
Set User Scaleable Pulse Output 
Configuration to either: 
System Ready/Thermostat Output or 
Valid/Thermostat Output 
DB25/DB37 pin 6 
 
5-24V, depending on 
User Input Voltage 
 
The Thermostat Output turns on (voltage high) when the internal gauge 
temperature rises above 40ºC, and turns off when the internal gauge 
decreases below 35ºC. 
The output can 
be connected to 
an electrically 
operated valve 
as shown.