Regency FG39 FireGenie Freestanding Gas Stove
13
Diagram  5
Note: If installing termination on a siding cov-
ered wall, a vinyl siding standoff or furring
strips  must  be  used  to  ensure  that  the
termination is not recessed into the siding.
The four wood screws provided should be
replaced  with  appropriate  fasteners  for
stucco,  brick,  concrete,  or  other  types  of
sidings.
5) Before connecting the horizontal run of flue
pipe to the flue termination, slide the black
decorative wall thimble cover over the flue
pipe, then slide the Wall Thimble (Part # 942)
over the flue pipe.
6) Slide the appliance and flue assembly to-
wards the wall carefully inserting the flue
pipe into the flue cap assembly. It is impor-
tant that the flue pipe extends into the flue
cap a sufficient distance so as to result in
a  minimum  pipe  overlap  of  1-1/4  inches
(32mm) . Secure the connection between
the flue pipe and the flue cap  using sheet
metal screws provided.  See diagram 6.
FG39: 59-3/4" (1518mm)
Diagram  2
b) The location of the horizontal flue ter-
mination on an exterior wall must meet
all  local  and  national  building  codes,
and must not be blocked or obstructed.
For  External  Flue  Termination  Loca-
tions, see diagram on page 8.
4) If installing the flue termination to a wall with
vinyl siding, the Vinyl Siding Standoff must
be used. Attach the Vinyl Siding Standoff
to the Horizontal Flue Termination, but first
run a bead of non-hardening mastic around
its  outside  edges,  so  as  to  make  a  seal
between flue cap and the standoff. Install
the Vinyl Siding Standoff (Part # 950) be-
tween  the  flue  cap  and  the  exterior  wall
and  attach  with  the  four  wood  screws
provided.  Seal  around  the  Vinyl  Siding
Standoff on all four sides. Diagram 5.   The
arrow on the flue cap should be point-
ing  up.  Insure  that  the  1-1/4"  (32mm)
clearances  to  combustible  materials  are
maintained. See diagram 5.
line  of  the  horizontal  pipe,  as  shown  in
diagram 2. Cut and frame the 10 inch (254mm)
square hole in the exterior wall where the
flue  will  be  terminated.  If  the  wall  being
penetrated is constructed of non-combus-
tible  material,  i.e.  masonry  block  or  con-
crete, a 7" (178mm) diameter hole is accept-
able.
Note:
a)
The horizontal run of flue should have
a 1/4 inch (6mm) rise for every 1 foot
(.3m)  of  run  towards  the  termination.
Never allow the flue to run downward.
This  could  cause  high  temperatures
and may present the possibility of a fire.
INSTALLATION
DURA-FLUE
HORIZONTAL
INSTALLATIONS
1) Set the unit in its desired location. Check to
determine if wall studs or roof rafters are
in  the  way  when  the  fluing  system  is
attached. If this is the case, you may want
to adjust the location of the unit.
2) Room Sealed pipe and fittings are designed
with special twist-lock connections to con-
nect the fluing system to the appliance flue
outlet.  A  twist-lock  appliance  adaptor  is
installed on the unit at the fac-
tory.  Assemble  the  desired
combination  of  pipe  and  el-
bows to the appliance
adaptor  with  pipe
seams  oriented  to-
wards the wall or ceil-
ing,  as  much  out  of
view as possible. The
final positioning of the
pipe and 90
o
 elbow as-
sembly is deter-
mined  by  the
mounting  orien-
tation  of  the
adaptor  on  the
stove and twist-
locked for a sol-
id connection.
Note:
a) Twist-lock  procedure:  Four  indenta-
tions,  located  on  the  female  ends  of
pipes and fittings, are designed to slide
straight onto the male ends of adjacent
pipes and fittings, by orienting the four
Diagram  1
945BG
45
O
  Elbow-Swivel-Black
990
90
Elbow Galv.
990B
90
O
  Elbow-Black
990G
90
Elbow-Swivel  Galv.
990BG
90
O
  Elbow-Swivel-Black
991
High Wind Term. Cap (Vertical)
980
Vertical Term. Cap
982
Snorkel-14" Rise Term.Cap
981
Snorkel-36" Rise Term.Cap
940
Wall Thimble-Support/Box
941
Cathedral/Ceiling-Support/Box
3951
Brass Trim-Wall Thimble/
Ceiling Support
963
Firestop  Spacer
943
Flashing 0/12-6/12
943S
Flashing 7/12-12/12
953
Storm Collar
950
Vinyl Siding Standoff
988
Wall Strap
942
Wall Thimble
Parts  not  supplied  by  Dura-Flue
946-506/P Flue Guard (Optional)
948-128
Vinyl Siding Shield
Astro  Cap  (Australian)
pipe  indentations  so  they  match  and
slide in to the four entry slots on the male
ends (diagram 1). Push the pipe sec-
tions completely  together, then twist-
lock  one  section  clockwise  approxi-
mately  one-quarter  turn,  until  the  two
sections  are  fully  locked.  The  female
locking lugs will not be visible from the
outside  on  the  Black  Pipe  or  fittings.
They may be located by examining the
inside of the female ends. Apply sealant
"Mill-Pac" to inner pipe and high temp
silicone sealant to outer pipe on every
twist-lock  joint.
Hint: Apply silicone to female end.
b) Horizontal runs of flue must be support-
ed  every  three  feet.  Wall  straps  are
available for this purpose.
3) With the pipe attached to the stove, slide the
stove into its correct location, and mark the
wall for a 10" x 10"  / 254mm x 254mm (inside
dimensions) square hole. The center of the
square hole should line up with the center-