INSTALLATION
Offset Chart
Diagram  13
Notes:
a) For multistorey vertical installations, a
Ceiling Fire stop (Part # 963) is required
at  the  second  floor,  and  any  subse-
quent floor. Diagram 13.  The opening
should be framed to 10 " x 10" (254mm
x  254mm)  inside  dimensions,  in  the
same manner as shown in diagram 10.
b) Any  occupied  areas  above  the  first  floor,
including  closets  and  storage  spaces,
through  which  the  vertical  flue  passes,
must be enclosed.
CATHEDRAL  CEILINGS
Round Support (RDS) &
Square Support (SQS)
If your home has a cathedral ceiling (no attic
space between the ceiling and the roof), install
the chimney and support as follows.
1) Situate the chimney in a convenient loca-
tion as near as possible to the appliance
outlet.  Cut and frame a hole in the roof for
the support. The sides of this hole must be
vertical with 1 1/4" (32mm) clearance.
2) Place the support in the opening. Lower it
to the correct height as determined by the
table and diagram below.
Using  a  level,  make  sure  the  support  is
vertical.  If the support extends above the
roof, cut it flush with the top of the roof.  Nail
the support to the frame opening using (8)
3" (76mm) spiral nails or #8 x 1-1/2" (38mm)
screws.
Note: If  you  are  using  a  6"  square  sup-
port  you  may  find  it  difficult  to
screw it in place because it is fairly
small  inside.
Simpson  Dura-Flue  has  provided  angle
brackets  with  this  support  which  can  be
screwed to the outside of the support box
and nailed to surrounding framing as re-
quired.  Use a minimum of four #8 x 1/2"
(13mm)  screws  per  bracket.    In  some
cases  these  brackets  may  need  to  be
trimmed (e.g.: to fit under a flashing).  Place
the  Finish  Collar  around  the  support  and
fasten  it  to  the  ceiling  using  the  screws
provided.
3) Use  appropriate  roof  flashing.    Place  the
flashing under the upper shingles and on
top of the lower shingles approximately half
of the flashing should be under the shin-
gles.
4) Assemble the desired lengths of Black Pipe
and  Elbows  necessary  to  reach  from  the
appliance adaptor up through the support
box and flashing to proper height as per Dia.
12, local codes or page 9.  Ensure that all
pipe and elbow connections are in their fully
twist  lock  position.
5) Ensure flue is vertical and secure flashing
to the roof  with roofing nails.  Slide the storm
collar over the pipe section and seal with a
mastic.
6) Twist lock the flue cap on to the last section.
Support Extensions - Round
(RDSE) or Square (SQSE)
Steep  pitched  cathedral  ceilings  may  require
the use of a support extension. This piece fits
down inside the support and can be adjusted
to increase the support's length by up to 22"
(559mm).  The  extension  is  attached  to  the
support using the eight metal screws provided.
Be sure there is at least a 2 inch overlap where
the extension joins the support.
    Slope
"X"
0/12 - 2/12               4" (102mm)
2/12 - 7/12            5-1/2" (140mm)
7/12 - 12/12          6-3/4" (172mm)
12/12 - 24/12          7-1/2" (191mm)
24/12+                  12-1/2" (378mm)
1-1/4" (32mm) Min.
1-1/4" (32mm) Min.
1-1/4"
(32mm)
Min.
1-1/4" (32mm) Min.
nails
Ceiling Firestop