Regency FG39 FireGenie Freestanding Gas Stove
INSTALLATION
GAS  CONNECTION
The gas line should be rigid pipe. Copper may
also be used if approved by AS5601-2004.
The gas connection at the valve is 1/2 male. For
minimum and maximum supply pressure see the
System Data Table.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual  shut-off  valve  during  any  pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa).    Disconnect  piping  from  valve  at  pres-
sures over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point.
Note: To  properly  check  gas  pressure,
both inlet and manifold pressures
should be checked using the valve
pressure  ports  on  the  valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure  tap(s),  turning  counterclockwise
with  a  1/8"  (3mm)  wide  flat  screwdriver.
3) Attach  manometer  to  "IN"  and/or  "OUT"
pressure  tap(s)  using  a  5/16"  (8mm)  ID
hose.
4) Seal and or check the pilot outlet (# 8)
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
6) When finished reading manometer, turn off
the  gas  valve,  disconnect  the  hose  and
tighten  the  screw  (clockwise)  with  a  1/8"
(3mm)  flat  screwdriver.  Screw  should  be
snug, but do not over tighten.
S.I.T. Valve Description
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection  for  Pressure  Regulator/Com-
bustion Chamber Compensation
6) Pressure Regulator for Minimum and Max-
imum Outlet Pressure
AERATION
ADJUSTMENT
The burner aeration is factory set but may need
adjusting due to either the local gas supply or
altitude.
FG39 with 40 mj.
FG39-NG
Fully Open
FG39-LPG
Fully Open
FG39 with 31 mj.
FG39-NG
6 mm Open
FG39-LPG
10 mm Open
Caution: Carbon will be produced if the air
shutter  is  closed  too  much.
Note: Any  damage  due  to  carboning  re-
sulting  from  improperly  setting  the
aeration  controls  is  NOT  covered
under  warranty.
Burner Inlet Orifice Sizes:
                   NG
       LPG
Burner
 #32
       #50
2.95mm     1.78mm
Max.  Input NG
40 Mj/h
LPG
38 Mj/h
Min.  Input NG
20 Mj/h
LPG
19 Mj/h
Supply  Pressure
NG
min.  1.13 kPa
LPG
min. 2.75 kPa
Manifold  Pressure
NG
.94 kPa
LPG
2.55kPa
Electrical: 240 V. 1.13A  60Hz.
Circulation: 2 speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 7 per set.
System Data
FG39 Converted to 31mj.
Burner Inlet Orifice Sizes:
NG
#37   2.65mm
LPG
#52   1.6mm
Max. Input - NG/LPG
31 Mj/h
Min. Input - NG/LPG
16 Mj/h
Supply  Pressure
NG
min.  1.13 kPa
LPG
min. 2.75 kPa
Manifold  Pressure
NG
.89 kPa
LPG
2.55kPa
Electrical: 240 V. 1.13A  60Hz.
Circulation: Variable speed fan, 125/75 CFM.
Log Set: Ceramic fiber, 7 per set.
System Data
FG39 with 40mj.
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet