INSTALLATION CLEARANCES
These boilers are approved for installation on combustible flooring 
in an alcove with minimum clearance to combustibles of:
TABLE 4
HW
300
HW
399
HW
420
HW
520
HW
610 & 670
TOP
28" (711.2) 32" (812.8) 24" (609.6) 24" (609.6) 24" (609.6)
SIDES
6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)
REAR
6" (152.4) 6" (152.4) 24" (609.6) 24" (609.6) 24" (609.6)
VENT
6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4) 6" (152.4)
Two  inch  (50.8mm)  clearance  is  allowable  from  combustible 
construction for hot water pipes.
Sufficient area should be provided at the front and rear of the unit 
for proper servicing.  Clearances of  24 inches (609.4mm) in the 
rear and 48 inches (1,219mm)  in the front are required by code.  
In a utility room installation, the door shall be wide enough to allow 
the boiler to enter or to permit the replacement of another appliance 
such as a water heater.
LEVELING
Each unit should be checked after installation to be certain that it is level.
If the unit is not level, insert metal shims under the legs of the unit 
to correct this condition.
SYSTEM CONNECTIONS
The  system  installation  must  conform  to  these  instructions 
and  to  the  requirements  of  the  local  code  authority  having 
jurisdiction.  Good  practice  requires  that  all  heavy  piping  be 
supported.
VENTING
A TYPICAL BOILER INSTALLATION
FIGURE 7.
VENTING THE BOILER - STANDARD VENTING
  WARNING
THE  INSTRUCTIONS  IN  THIS  SECTION  ON  VENTING 
THE  BOILER  MUST  BE  FOLLOWED  TO  AVOID  CHOKED 
COMBUSTION  OR  RECIRCULATION  OF  FLUE  GASES.  
SUCH CONDITIONS CAUSE SOOTING OR RISKS OF FIRE 
AND ASPHYXIATION.
TYPE B VENTING MAY BE USED WITH THESE BOILERS.  ALL 
LOCAL  UTILITY  REGULATIONS  ON  VENTING  SHOULD  BE 
FOLLOWED.
For boilers for connection to gas vents or chimneys, vent sizing, 
installation  and  termination  shall  be  in  accordance  with  the 
current edition of the National Fuel Gas Code, ANSI Z223.1, or 
CAN/CSA B149.1, Installation Codes, or applicable provisions 
of the local building codes.
Vent connectors serving appliances vented by natural draft shall 
not be connected into any portion of mechanical draft systems 
operating under positive pressure.
The minimum distance from adjacent public walkways, adjacent 
buildings, openable windows and building openings shall not be 
less than those values specified in the National Fuel Gas Code, 
ANSI Z223.1 and/or CAN/CSA B149.1, Installation Codes;
Stack or chimney must be a minimum height of 12" (305mm) 
above the annual snow fall to prevent blockage.