Water Temperature
Time to Produce 2nd & 3rd 
Degree Burns on Adult Skin
OVER: 170°F (77°C)
160°F (71°C)
150°F (65°C)
140°F (60°C)
130°F (54°C)
120°F (49°C)
Nearly Instantaneous
About 1/2 second
About 1-1/2 seconds
Less than 5 seconds
About 30 seconds
More than 5 minutes
USE ANTI-SCALD VALVE(S) in the hot water system to reduce 
the risks of scalds at points of use such as lavatories, sinks 
and bathing facilities.
A change in water temperature in the storage tank lower than 
the Tank Temperature Control setting will cause the sensor to 
close its contacts and consequently energize the boiler.
If the Tank Temperature Control is out of calibration, replace it 
with a new one; do not attempt to fix this control.
  WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 
TO  SHUT  OFF,  TURN  OFF  THE  MANUAL  GAS  CONTROL 
VALVE TO THE APPLIANCE.
GENERAL
THERMOMETERS
Thermometers should be obtained and field installed as shown 
in the installation diagrams.
Thermometers  are  installed  in  the  system  as  a  means  
of  detecting  a  possible  liming  condition  in  the  boiler.  
An  increase  of  5°F  (3°C)  over  the  normal  temperature  
rise  through  the  boiler  is  an  indication  that  lime  is  
p r e s e n t .   T h e   t e r m   " t e m p e r a t u r e   r i s e "   d e s i g n a t e s  
the  difference  between  the  boiler  inlet  and  outlet  water 
temperature.
An  increase  of  5°F  (3°C)  above  the  recorded  temperature  
rise  may  signify  a  liming  condition  in  the  coils  or  heat  
e x c h a n g e r.   R e f e r   t o   C L E A N I N G   A N D   F L U S H I N G  
section of this manual for deliming instructions.
Record  temperature  rise  at  initial  star t-up  for  future 
reference.
DRAIN VALVE (Not Supplied)
A drain valve must be obtained and installed on each boiler 
and  tank  for  draining  purposes,  see  installation  diagrams  in 
this manual.
REQUIRED ABILITY
Installation or service of this boiler requires ability equivalent to that 
of a licensed tradesman in the field involved. Plumbing, air supply, 
venting, gas supply and electrical work are required.
LOCATION
When installing the boiler, consideration must be given to proper 
location. Location selected should be as close to the stack or chimney 
as practicable with adequate air supply and as centralized with the 
piping system as possible. This location should also be such that the 
gas ignition system components are protected from water (dripping, 
spraying, etc.) during appliance operation and service (circulator 
replacement, control replacement, etc.).
THE BOILER MUST NOT BE INSTALLED ON CARPETING.
THE BOILER SHOULD NOT BE LOCATED IN AN AREA WHERE 
IT WILL BE SUBJECT TO FREEZING.
LOCATE IT NEAR A FLOOR DRAIN. THE BOILER SHOULD BE 
LOCATED IN AN AREA WHERE LEAKAGE FROM THE BOILER OR 
CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE ADJACENT 
AREA OR TO LOWER FLOORS OF THE STRUCTURE.
WHEN  SUCH  LOCATIONS  CANNOT  BE AVOIDED, A  METAL 
DRAIN PAN SHOULD BE INSTALLED UNDER THE BOILER. Such 
pans should be fabricated with sides at least 60mm (2-1/2") deep, 
with length and width at least 50mm (2") greater than the diameter 
of the boiler and must be piped to an adequate drain. The pan must 
not restrict combustion air flow.
  
 WARNING
KEEPING BOILER AREA CLEAR AND FREE FROM COMBUSTIBLE 
MATERIALS, GASOLINE AND OTHER FLAMMABLE VAPORS AND 
LIQUIDS.
 
 WARNING
THERE  IS A  RISK  IN  USING  FUEL  BURNING APPLIANCES 
SUCH AS BOILERS IN ROOMS OR AREAS WHERE GASOLINE, 
OTHER FLAMMABLE LIQUIDS OR ENGINE DRIVEN EQUIPMENT 
OR  VEHICLES ARE  STORED,  OPERATED  OR  REPAIRED. 
FLAMMABLE VAPORS ARE HEAVY AND TRAVEL ALONG THE 
FLOOR AND MAY BE IGNITED BY THE IGNITER OR MAIN BURNER 
FLAMES CAUSING FIRE OR EXPLOSION. SOME LOCAL CODES