A.O. Smith HW 610 ユーザーズマニュアル

ページ / 56
18
1. CONVENTIONAL INSTALLATIONS
All modern hydronic type boilers are exceptionally fast heating units.  
The  low  water  volumes  in  relation  to  firing  rates  require  special 
attention to water flow rates for smooth, efficient operation. These 
considerations for the A. O. Smith copper heat exchanger boilers 
are covered below.
Conventional 20
0
F (10
0
C) drop in systems for a fully loaded boiler 
will maintain the following approximate flow rates:
MODELS
GPM (LPM)
HW-300
23 (87)
HW-399
30 (114)
HW-420
35 (132)
HW-520
39 (148)
HW-610/670
46 (175)
Figure 7 on page 14 shows a typical installation of the boiler with pipe 
sizing and circulator selected by the installer to provide adequate 
water flow whenever the boiler is firing.
In a system with several large zones of which any might be smaller 
than  approximately  1/3  of  the  system  should  include  a  hydronic 
balancer  as  shown  in  Figure  7. The  balancer  connects  between 
the  system  supply  and  the  return  line  before  the  circulator  inlet. 
Adjustment of the balancing cock should permit adequate boiler flow 
rate when only the smallest zone is in operation.
Attention should be given to balancing inputs and water flow rates 
where wide variations of system flow rates can occur.
The recommended minimum flow rates that will result in approximately 
50
0
F (30
0
C) temperature rise across the boiler are as follows:
MODELS
GPM (LPM)
HW-300
9 (34)
HW-399
12 (45)
HW-420
14 (53)
HW-520
16 (61)
HW-610
18 (69)
HW-670
20 (76)
If system flow rate is unknown, or if zoning creates extreme variations 
in flow rates, the boiler should be installed as shown in Figure 11 on 
this page for A. O. Smith LINEAR-TEMP installations.
2. LINEAR-TEMP INSTALLATIONS
 
A.  New Installations
A. O. Smith LINEAR-TEMP systems have been designed to provide 
efficient, trouble-free operation of the boiler sizes covered in this 
manual with any of the following conditions:
 
a.  Unknown system flow rate
 
b.  Varying flow rate as with zoned systems
 
c.  Multiple boiler installations
Figure 11 on this page shows piping and accessory arrangement 
for a boiler pumped independent of the primary system mains.  Pipe 
sizing and boiler loop pump selection data are shown in Table 6 for 
several different temperature rises across the boilers.
ONE BOILER INSTALLED
INDEPENDENT OF THE PRIMARY SYSTEM
FIGURE 11.
Total heating requirements for the building can be supplied by a 
series of boiler loops all connecting to a common pipe joining the 
system supply and return mains. The supply and return branches of 
each boiler loop must join the common pipe only a short nipple length 
apart. The different sets of branches should be installed reasonably 
close  together,  but  not  necessarily  to  the  short  nipple  length  as 
required for the supply and return of each set. These branches may 
be made with tees or with welded connections.
The installer is reminded that the total boiler flow rates need not 
match the system flow rate.
TABLE 6.
PUMP AND PIPE SIZING DATA
(PIPING FROM TEES IN MAIN TO BOILER BRANCHES)
Model
Temp. Rise °F (°C) G.P.M. *Pump Size Pipe Size
HW-300
 20 (10)
 30 (15)
 30 (15)
40 (20)
23
15
15
11
1-1/2" PR
150
125
100
2"
1-1/2"
1-1/4"
1"
HW-399
20 (10)
35 (15)
40 (20)
40 (20)
30
20
15
15
60-13
1-1/2" HV
150
125
2"
1-1/2"
1-1/2"
1-1/4"
HW-420
20 (10)
35 (15)
40 (20)
40 (20)
32
21
16
16
60-13
1-1/2" HV
150
125
2"
1-1/2"
1-1/2"
1-1/4"
HW-520
20 (10)
20 (10)
35 (17)
40 (20)
39
26
23
20
2-1/2"
1-1/2" HV
1-1/2" HV
150
2-1/2"
2"
1-1/2"
1-1/2"
HW-610/670
20 (10)
30 (15)
35 (17)
40 (20)
51
34
29
25
60-13
2-1/2"
2"
1-1/2" HV
3"
2-1/2"
2"
1-1/2"
NOTE:   Pipe loop sizes and pump selections based on 
 
 50 equivalent feet of pipe and fittings.
*All pump sizes listed are B & G model numbers.
SYSTEM INSTALLATIONS