5. VENT VALVES
It is recommended that automatic, loose key or screwdriver type 
vent valves be installed at each convector or radiator.
6. MANIFOLD HEADERS
Split systems with individual supply and return lines from the boiler 
room  should  normally  have  this  piping  connected  to  supply  and 
return  manifold  headers  near  the  boiler. To  achieve  good  water 
distribution  with  maximum  pressure  drop  for  several  circuits, 
manifolds  of  at  least  2-1/2"  (64mm)  diameter  are  suggested  on 
HW-399, HW-420, HW-520, HW-610 and HW-670 units.  HW-300 
units should have 1-1/2" (38mm) diameter manifolds.
The  circuits  should  be  spaced  on  the  header  at  a  minimum  of  
3" (76mm) center to center. Install a balancing cock in each return line.
Manifold headers are recommended for split systems with or without 
zone valves and also those installations with zone circulators.  If the 
system is to be split at remote points, good practice requires special 
attention be given to main pipe sizing to allow balancing of water flow.
The boiler piping system of a hot water boiler connected to heating 
coils located in air handling units where they may be exposed to 
refrigerated air circulation must be equipped with flow control valves or 
other automatic means to prevent gravity circulation of the boiler water 
during the cooling cycle.
7. COOLING PIPING
When the boiler is used in conjunction with a refrigeration system it 
must be installed so that the chilled medium is piped in parallel with 
the boiler with appropriate valves to prevent the chilled medium from 
entering the boiler, see Figure 13.
Water temperature in the heating system must be reduced to less 
than 100
0
F (38°C) before cooling system is started, or damage to 
the chiller unit may occur.
SCHEMATIC SHOWING PROPER PIPING ISOLATION
OF THE BOILER FROM THE CHILLER
FIGURE 13.
If the boiler is connected to chilled water piping or its heating coils 
are exposed to refrigerated air, the boiler piping system must be 
equipped with flow valves or other automatic means to prevent gravity 
circulation through the boiler during the cooling cycle.
8. CIRCULATING PUMP
CONSTANT CIRCULATING PUMP OPERATION OF THE BOILER 
VOIDS THE  WARRANTY.  Constant  water  flow  through  the  unit 
will  “wash”  away  the  copper’s  natural  protective  coating. This  is 
called velocity erosion. This erosion is not as great a problem when 
intermittent  circulating  operation  is  used  per  the  recommended 
installation  procedure.  Constant  circulation  of  water  through  the 
building’s system main is permissible as long as the water does not 
constantly flow through the boiler. Only all bronze or stainless steel 
circulators are to be used with the unit when it is installed in HOT 
WATER SUPPLY SYSTEMS.
A TYPICAL CIRCULATING PUMP
FIGURE 14.
Although each circulator that requires oiling is oiled and operated by 
the manufacturer, IT MUST BE OILED AGAIN BEFORE OPERATED.  
Oil the three oil cups (2 on the motor, 1 on the pump) as instructed 
on the oil tube supplied with the unit, see Figure 14 on this page.
Thereafter, during the heating season, lubricate the three oil cups at 
least once every four months. Combination heating-cooling systems 
should be lubricated every four months year ‘round.
Use 2 or 3 teaspoonsful in bearing oil cups or 12 drops in the motor 
oil  cups,  see  Figure  14  on  this  page.  Use  No.  20  non-detergent 
motor oil.
Follow  the  same  oiling  procedure  if  a  replacement  circulator  is 
installed into the system.
GAS CONNECTIONS
 WARNING
THIS BOILER IS NOT INTENDED TO OPERATE AT GAS SUPPLY 
PRESSURE  OTHER THAN  SHOWN  ON THE  RATING  PLATE.  
EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE 
DAMAGE TO  GAS  VALVES  WHICH  CAN  RESULT  IN  FIRE  OR 
EXPLOSION.  IF OVERPRESSURE HAS OCCURRED SUCH AS 
THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY 
MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE 
CHECKED FOR SAFE OPERATION.  MAKE SURE THAT THE OUTSIDE 
VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT 
VALVES ARE PROTECTED AGAINST BLOCKAGE.  THESE ARE PARTS 
OF THE GAS SUPPLY SYSTEM, NOT THE BOILER.  VENT BLOCKAGE 
MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS.
WHEN  LOCAL  CODES  REQUIRE A  MAIN  MANUAL  SHUTOFF 
VALVE  OUTSIDE  THE  BOILER  JACKET, A  SUITABLE  MAIN 
MANUAL SHUTOFF VALVE MUST BE INSTALLED IN A LOCATION 
COMPLYING WITH THOSE CODES.
IT IS IMPORTANT TO GUARD AGAINST GAS VALVE FOULING 
FROM CONTAMINANTS IN THE GAS WAYS.  SUCH FOULING 
MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION.
IF  COPPER  SUPPLY  LINES  ARE  USED  THEY  MUST  BE 
CERTIFIED FOR GAS SERVICE.
BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS 
PIPE IS CLEAN ON THE INSIDE.