NO.
SUGGESTED ITEMS FOR INSTALLATION
1
Short  pipe  nipple  and  pair  of  boiler  loop  tees  in  piping 
between system supply and return. One set per each group 
of boilers.
2 Boiler pipe loop. See piping sizing data.
3 Boiler circulator. See pump sizing data.
4 Thermometer.
5 Theraltimeter.
6 Plug cock to control flow rate.
7 Safety  flow  switches.  For  interlock  with  other  systems  or 
instead of low water cutoff.
8 Relief valve.
9
With one -300, -399 or -420 item 9 is - sensing element of 
remote control.
With a group of -300's, -399's or -420's, item 9 is - for 1st 
boiler, the sensing element as above. For additional boilers, 
install  a  2nd  limit  control  if  required  by  local  codes.  With 
any -520, -610 or 670 boilers, install 2nd limit control here if 
required by local code.
BOILER INLET - OUTLET SIZES
10 HW-300  -  1-1/4",  HW-399  -  1-1/2",  HW-420  -  1-1/2",  
HW-520 & HW-610 - 2".
10 HW-300 - 1-1/4", HW-399 - 1-1/2", HW-420 - 1-1/2", HW-520 
& HW-670 - 2".
MINIMUM BRANCH SIZES TO BOILERS
11
HW-300 - 1-1/4"               HW-520, 610 (Single boiler
HW-399 - 1-1/2"               per pump) 2"
HW-420 - 1-1/2"               
11
HW-300 - 1-1/4"               HW-520, 670 (Single boiler
HW-399 - 1-1/2"               per pump) 2"
HW-420 - 1-1/2"               
12
Flow  control  valve.  Required  only  if  flow  rate  of  system 
primary is excessive for size of boiler branch tees or if chilled 
water main is above boilers.
13 System supply temperature thermometer.
14 Boiler headers for three (3) boilers can be larger than pipe 
loop, if desired, to aid in balancing.
The  system  flow  rate  is  selected  to  give  the  desired  system 
temperature drop - depending on the design criteria.
The  boiler  generator  flow  rates,  on  the  other  hand,  should  be 
selected to give the temperature rise through the generator that is 
both economical and offers the best generator efficiency.
The boiler temperature rise is normally between 10
0
C and 20
0
C (20
0
and 40
0
F). The system temperature that will be introduced to the 
boiler (inlet temperature) plus the selected boiler temperature rise 
selected from PUMP AND PIPE SIZING DATA should not exceed 
the high limit control setting of 115
0
C (240
0
F).
There should be a relation of the minimum system load to the size 
boiler selected as the first firing or base boiler. This will stabilize 
operation during minimum load periods.
 
B.  Commercial Boiler Replacements
Application of LINEAR-TEMP
®
 to a commercial boiler replacement 
with an old multiple pump installation is an excellent way to modernize 
the system. The A. O. Smith boiler(s) should be installed on a pipe 
loop with a separate circulating pump selected from PUMP AND 
PIPE SIZING DATA TABLE.
Figure 12 shows a line drawing of how the system headers should be 
connected to the pipe loop installed with the replacement boiler(s).  
Make-up water connections and accessories are not shown.
SCHEMATIC OF THE LINEAR-TEMP
®
 SYSTEM
FIGURE 12.
Supply and return headers of the old system should be connected 
to the boiler loop with a pair of tees set close together. The boiler 
loop pump and the boiler(s) should be wired to operate only when 
any of the system pumps are in operation. The number of zone 
pumps that may be in operation at any particular time will take 
their required flow rate out from the first tee in the boiler piping. 
This  water  will  be  circulated  through  the  proper  branches  from 
the supply header to the zones calling for heat. The water will be 
brought back to the return header and then into the second tee in 
the boiler pipe loop. There will be no conflict between the boiler 
pump and the zone pumps when the two tees in the boiler loop 
are placed close together.
Normal  use  of  flow  control  valves  is  required  to  prevent  cross 
circulation of zones as with any multiple pump system. Flow control 
is not required on boiler circuit.
Attention should be given to balancing gas inputs and water flow 
rates. Large systems with multiple boilers should include main water 
temperature control (with or without outdoor reset) to stage the boilers 
on and off in relation to the load on the system.
3. WATER SUPPLY LINE
These boilers can be used ONLY in a forced circulation hot water 
heating system. Since most forced circulation systems will be of 
the closed type, install the water supply line as shown on piping 
diagrams, Figure 7 to 11 on pages 14 and 18.
Fast  filling  of  large  pipe,  old  radiator  installations  and  pressure 
purging  of  series  loop  systems  (where  high  pressures  are  not 
available)  requires  bypassing  of  the  pressure  reducing  valve. 
Generally, pressure purging is not possible with a well pump system. 
High point air venting is essential.
If  the  system  is  of  the  open  type,  a  pressure  reducing  valve 
will not be required as the water supply to the system will be 
controlled  by  a  manually  operated  valve. An  overhead  surge 
tank is required.
4. EXPANSION TANK
 CAUTION
A closed system will exist if a check valve (without bypass), pressure 
reducing valve (without bypass), or a water meter (without bypass) is 
installed in the cold water line between the water heater and street 
main (or well).
Excessive pressure may develop causing premature tank failure or 
intermittent relief valve operation. This is not a warranty failure.  An 
expansion tank or a similar device may be required in the inlet supply 
line between the appliance and the meter or valve to compensate for 
the thermal expansion of water under supply pressure, see Figure 7 
on page 14.
An air separator as shown in the piping diagrams is recommended 
especially for modern commercial hydronic systems.