EXCEL 500/600 INSTALLATION INSTRUCTIONS 
XF522A and XF527 Analog Output Modules 
Technical Specifications 
Number: 
8 analog outputs 
Voltage rating: 
0 to 10 V, max. 11V 
Current rating: 
1 mA max. 
Resolution: 
8 bit 
Accuracy: 
±150 mV or 1.5% deviation from output voltage 
Manual override switches: 
XF522A 
5 manual override switches (AO1 to AO5) 
XF527 
No manual override switches 
Fig. 63. XF522A and XF527 Analog Output modules 
NOTE:  The maximum output current of 1 mA must not be 
exceeded. 
NOTE:  Both modules are fully pin compatible. 
XF524A and XF529 Digital Output Modules 
Technical Specifications 
Number: 
6 digital outputs 
Voltage rating: 
240 Vac max. per contact and per module 
Current rating: 
4 A max. per contact, 12A max. per module 
Relay contacts: 
K1 to K5: 
changeover contact (voltage-free) 
K6: 
normally open contact (voltage-free) 
Fig. 64. XF524A and XF529 Digital Output module 
NOTE:  Maximum voltage for U.S. is 24 V. 
NOTE:  Both modules are fully pin compatible. 
Beginning with V3.04.00 firmware, the online point attribute 
normally open/normally closed (NO/NC) defines the relation 
between the physical input signal and its logical status. See 
Table 10. 
Table 10. NO/NC attribute and output characteristic 
Relay On/Off 
NO/NC attribute 
Logical status 
On 
NO 
Off 
NO 
On 
NC 
Off 
NC 
EN1R-1047GE51 R0902 