Precision Trading 60 R3.0 ユーザーズマニュアル

ページ / 62
Operator Manual, Supercharger 60 
R3.0 
 
Page 22 of 62 
4.25  DS7B - OVR HEAT: 
 
4.25.1.  Indicates that the discharge bank is overheated. 
4.26  DS8A - VOLT FLT: 
 
Indicates voltage fault. 
4.26.1.  Continuous: battery connected with polarity reversed. 
4.26.2.  Flashing: (during charge) battery voltage in excess of 1.75 volts per cell or in 
excess of 85 volts, or open circuit. 
4.27  DS8B -CURR FLT: 
 
4.27.1.  Indicates that the actual current differs from the programmed value by more than 
1A. 
4.28  DS9 - CC   
 
 
4.28.1.  Indicates that the charger is in the basic Constant Current mode. 
4.29  DS10 - CV 
 
 
 
4.29.1.  Indicates that the charger is in the Constant Current/Float mode. 
4.30  DS11 - PEAK 
 
 
4.30.1.  Indicates that the charger is in the Constant Current/Peak mode. 
4.31  AUDIBLE ALARM: 
4.31.1.  Continuous: turns on with any of the faults. 
4.31.2.  Pulsating: turns on with cycle end.