R3.0 
 
Page 23 of 62 
5. 
MODES OF OPERATION 
5.1  CONSTANT CURRENT CHARGE 
5.1.1.  DUAL RATE: 
5.1.1.1.  The battery is charged at the main rate for a preset time, at the end of 
which, the current is switched automatically to the topping rate for the 
remainder of the total time selected. 
5.1.1.2.  Charging is automatically terminated at the end of the total time 
selected (cycle end), or as a fault if: 
•  Battery overtemperature is detected (Overtemp fault). 
•  Battery voltage is in excess of 1.75V/cell as determined by the 
number of cells programmed, or if battery voltage is in excess of 
85V (voltage fault). 
•  Actual charging current differs from the programmed value by 
more than 1 AMP (current fault). 
5.1.1.3.  Charge operation may be terminated at any time by depressing the 
RESET (green) button. 
5.1.2.  SINGLE RATE: 
5.1.2.1.  The battery is charged at the topping rate for a preset time. 
5.1.2.2.  Charging is automatically terminated at the end of the total time 
selected (cycle end), or as a fault if: 
•  Battery overtemperature is detected (Overtemp fault). 
•  Battery voltage is in excess of 1.75V/cell as determined by the 
number of cells programmed, or if battery voltage is in excess of 
85V (voltage fault). 
•  Actual charging current differs from the programmed value by 
more than 1 AMP (current fault). 
5.1.2.3.  Charge operation may be terminated at any time by depressing the 
(green) reset button.