Press the 
 button.
Press the “ENTER” button.
This is a typical first engine parameter page. The 
three values on this page are not able to be configured 
as other values. 
LINE 1:  Oil Temperature (Analog Channel #1) in 
degrees Fahrenheit.
LINE 2:  Oil Pressure (Analog Channel #3) in pounds 
per square inch.
LINE 3:  Coolant Temperature (Analog Channel #2) 
in degrees Fahrenheit.
LINE 4:  “More” field to allow page selection.
If any of these signals are not configured, they will dis-
play “n/a” for their value such as the Oil Temperature 
shown above.
Press the “ENTER” button.
This is a typical second engine parameter page. The 
first two values on this page are not able to be config-
ured as other values. 
LINE 1:  Engine RPM
LINE 2:  Battery Voltage in Volts DC. 
If any of these signals are not configured, they will 
display “n/a” for their value. 
LINE 3: Normally Battery Charger Current (Analog 
Channel #9). If it is not configured, the line will be 
blank.
LINE 4:  “More” field to allow page selection.
Press the “ENTER” button.
This is a typical third engine parameter page. 
LINE 1:  Total number of hours the engine has run. 
LINE 2:  Coolant Level Sensor (Analog Channel #4) 
reading in steps 0 - 1023. 
LINE 3:  Often the Fuel Level Sensor (Analog Channel 
#5) reading in %. As depicted, Analog Channel #5 is 
not configured – leaving the line blank.
LINE 4:  “More” field to allow page selection.
Press the “ENTER” button.
This is a typical fourth engine parameter page. 
LINE 1: Auxiliary Analog Channel input (Analog 
Channel #6). 
LINE 2: Throttle Position Sensor (Analog Channel 
#7) reading in steps 0 - 1023.
LINE 3: Emissions Sensor (Analog Channel #8) 
reading. As depicted, Analog Channels #6 and #8 are 
not configured – leaving the lines blank.
LINE 4:  “More” field to allow page selection.
  
15
General Information
H-100 Control Panel Technical Manual