There are two System Status pages. These pages 
show the system status, system time, and system 
versions.
Do the following to view the system status pages:
Press the “MENU” button.
Press the 
 button twice.
Press the “ENTER” button.
This is a typical first System Status page. 
LINE 1:  Engine Running Status. It can have the fol-
lowing values:
“Stopped, Key SW Off”
The engine is stopped and the key switch is in the 
OFF position.
“Running from Manual”
The engine is starting or running and the key switch 
is in the MANUAL position.
“Running from 2-wire”
The engine is starting or running because the 2-wire 
start signal was activated and the key switch is in the 
AUTO position.
“Running from serial”
The engine is starting or running because the GenLink 
commanded it to start and the key switch is in the 
AUTO position.
“Running exercise”
The engine is starting or running because internal 
exercise was activated and the key switch is in the 
AUTO position.
“Stopped, Key SW Auto”
The engine is stopped and the key switch is in the 
AUTO position.
“Running, QuietTest”
The engine is starting or running because QuietTest® 
was activated and the key switch is in the AUTO posi-
tion.
“Running, HTS Xfer SW”
The engine is starting or running because the HTS(s) 
indicated a need for the generator power and the key 
switch is in the AUTO position.
LINE 2:  Generator Status. It can have the following 
values:
“Resetting”
The generator control system is resetting.
“Stopped”
Generator is stopped and not preheating.
“Stopped, Preheating “
Generator is stopped and preheating.
“Cranking”
Generator is starting and not preheating.
“Cranking, Preheating”
Generator is starting and preheating.
“Pause between starts”
Generator is pausing between consecutive start 
attempts.
“Started,not to speed”
Generator is started, but has not attained normal 
running speed yet.
“Warming, Alarms Off “
Generator is started and is up to speed, but is waiting 
for warmup timer to expire.
“Warmed Up,Alarms Off”
Generator is started and warmed up, but the hold-off 
alarms are not yet enabled.
“Warming, Alarms On”
Generator is started and the hold-off alarms are 
enabled, but is waiting for warmup timer to expire.