H-100 DIGITAL OUTPUT FUNCTIONS
  Number 
Default Function Name 
Function Description
 
COMMON ALARM 
An alarm is active
 
COMMON WARNING 
A warning is active
 
GEN RUNNING 
Generator is running
 
ALARMS ENABLED 
All alarm hold off delays have expired, so all alarms are enabled
 
READY FOR LOAD 
Generator is warmed up and ready to accept power loading
 
GEN READY TO RUN 
Generator is ready to start
 
GEN STOPPED-ALRM 
Generator stopped due to a shutdown alarm
 
GEN STOPPED 
Generator is stopped
 
GEN IN MANUAL 
Generator in MANUAL mode ( key switch in MANUAL or ILC overriden)
 
10 
GEN IN AUTO 
Generator in AUTO mode ( key switch in AUTO or ILC overriden )
 
11 
GEN IN OFF 
Generator in OFF mode ( key switch in OFF or ILC overriden )
 
12 
OVERCRANK ALARM 
Generator has unsuccessfully tried to start the designated number of times
 
13 
OIL INHIBIT ALRM 
Oil pressure too high for a stopped engine
 
14 
ANNUNC SPR LIGHT 
ILC controlled: this function operates the spare remote annunciator light
 
15 
OIL TEMP HI ALRM 
Oil Temperature has gone above maximum alarm limit
 
16 
OIL TEMP LO ALRM 
Oil Temperature has gone below minimum alarm limit
 
17 
OIL TEMP HI WARN 
Oil Temperature has gone above maximum warning limit
 
18 
OIL TEMP LO WARN 
Oil Temperature has gone below maximum warning limit
 
19 
OIL TEMP FAULT 
Oil Temperature sensor exceeds nominal limits for valid sensor reading
 
20 
COOL TMP HI ALRM 
Coolant Temperature has gone above maximum alarm limit
 
21 
COOL TMP LO ALRM 
Coolant Temperature has gone below minimum alarm limit
 
22 
COOL TMP HI WARN 
Coolant Temperature has gone above maximum warning limit
 
23 
COOL TMP LO WARN 
Coolant Temperature has gone below maximum warning limit
 
24 
COOL TMP FAULT 
Coolant Temperature sensor exceeds nominal limits for valid sensor reading
 
25 
OIL PRES HI ALRM 
Oil Pressure has gone above maximum alarm limit
 
26 
OIL PRES LO ALRM 
Oil Pressure has gone below minimum alarm limit
 
27 
OIL PRES HI WARN 
Oil Pressure has gone above maximum warning limit
 
28 
OIL PRES LO WARN 
Oil Pressure has gone below maximum warning limit
 
29 
OIL PRES FAULT 
Oil Pressure sensor exceeds nominal limits for valid sensor reading
 
30 
COOL LVL HI ALRM 
Coolant Level has gone above maximum alarm limit
 
31 
COOL LVL LO ALRM 
Coolant Level has gone below minimum alarm limit
 
32 
COOL LVL HI WARN 
Coolant Level has gone above maximum warning limit
 
33 
COOL LVL LO WARN  
Coolant Level has gone below maximum warning limit
 
34 
COOL LVL FAULT 
Coolant Level sensor exceeds nominal limits for valid sensor reading
 
35 
ANALOG 5 HI ALRM 
Analog Input #5 has gone above maximum alarm limit
 
 
FUEL LVL HI ALRM 
Fuel Level
 
36 
ANALOG 5 LO ALRM 
Analog Input #5 has gone below minimum alarm limit
 
 
FUEL LVL LO ALRM 
Fuel Level
 
37 
ANALOG 5 HI WARN 
Analog Input #5 has gone above maximum warning limit
 
 
FUEL LVL HI WARN 
Fuel Level
 
38 
ANALOG 5 LO WARN 
Analog Input #5 has gone below maximum warning limit
 
 
FUEL LVL LO WARN 
Fuel Level
 
39 
ANALOG 5 FAULT 
Analog Input #5 sensor exceeds nominal limits for valid sensor reading
 
 
FUEL LVL FAULT 
Fuel Level
 
40 
ANALOG 6 HI ALRM 
Analog Input #6 has gone above maximum alarm limit
 
 
FUEL PRS HI ALRM 
Fuel Pressure
 
 
INLT TMP HI ALRM 
Inlet Air Temperature
 
41 
ANALOG 6 LO ALRM 
Analog Input #6 has gone below minimum alarm limit
 
 
FUEL PRS LO ALRM 
Fuel Pressure
 
 
INLT TMP LO ALRM 
Inlet Air Temperature
‹
 42
Appendix B
H-100 Control Panel Technical Manual