Generac Power Systems H-100 사용자 설명서

다운로드
페이지 52
  
43
  Number 
Default Function Name 
Function Description
 
42 
ANALOG 6 HI WARN 
Analog Input #6 has gone above maximum warning limit
 
 
FUEL PRS HI WARN 
Fuel Pressure
 
 
INLT TMP HI WARN 
Inlet Air Temperature
 
43 
ANALOG 6 LO WARN 
Analog Input #6 has gone below maximum warning limit
 
 
FUEL PRS LO WARN 
Fuel Pressure
 
 
INLT TMP LO WARN 
Inlet Air Temperature
 
44 
ANALOG 6 FAULT 
Analog Input #6 sensor exceeds nominal limits for valid sensor reading
 
 
FUEL PRS FAULT 
Fuel Pressure
  
INLT 
TMP 
FAULT 
Inlet 
Air 
Temperature
 
45 
ANALOG 7 HI ALRM 
Analog Input #7 has gone above maximum alarm limit
 
 
GOV POS HI ALARM 
Throttle Position
 
46 
ANALOG 7 LO ALRM 
Analog Input #7 has gone below minimum alarm limit
 
 
GOV POS LO ALARM 
Throttle Position
 
47 
ANALOG 7 HI WARN 
Analog Input #7 has gone above maximum warning limit
 
 
GOV POS HI WARN 
Throttle Position
 
48 
ANALOG 7 LO WARN 
Analog Input #7 has gone below maximum warning limit
 
 
GOV POS LO WARN 
Throttle Position
 
49 
ANALOG 7 FAULT 
Analog Input #7 sensor exceeds nominal limits for valid sensor reading
 
 
GOV POS FAULT 
Throttle Position
 
50 
ANALOG 8 HI ALRM 
Analog Input #8 has gone above maximum alarm limit
 
 
OXYGEN HI ALARM 
Emissions Sensor
 
 
FLUID BS HI ALRM 
Fluid Basin
 
51 
ANALOG 8 LO ALRM 
Analog Input #8 has gone below minimum alarm limit
 
 
OXYGEN LO ALRM 
Emissions Sensor
 
 
FLUID BS LO ALRM 
Fluid Basin
 
52 
ANALOG 8 HI WARN 
Analog Input #8 has gone above maximum warning limit
  
OXYGEN 
HI 
WARN 
Emissions 
Sensor
 
 
FLUID BS HI WARN 
Fluid Basin
 
53 
ANALOG 8 LO WARN 
Analog Input #8 has gone below maximum warning limit
 
 
OXYGEN LO WARN 
Emissions Sensor
 
 
FLUID BS LO WARN 
Fluid Basin
 
54 
ANALOG 8 FAULT 
Analog Input #8 sensor exceeds nominal limits for valid sensor reading
 
 
O2 SENSOR FAULT 
Emissions Sensor
 
 
FLUID BS FAULT 
Fluid Basin
 
55 
ANALOG 9 HI ALRM 
Analog Input #9 has gone above maximum alarm limit
 
 
CHG CURR HI ALRM 
Battery Charge Current
 
56 
ANALOG 9 LO ALRM 
Analog Input #9 has gone below minimum alarm limit
 
 
CHG CURR LO ALRM 
Battery Charge Current
 
57 
ANALOG 9 HI WARN 
Analog Input #9 has gone above maximum warning limit
 
 
CHG CURR HI WARN 
Battery Charge Current
 
58 
ANALOG 9 LO WARN 
Analog Input #9 has gone below maximum warning limit
 
 
CHG CURR LO WARN 
Battery Charge Current
 
59 
ANALOG 9 FAULT 
Analog Input #9 sensor exceeds nominal limits for valid sensor reading
 
 
CHG CURR FAULT 
Battery Charge Current
 
60 
BAT VOLT HI ALRM 
Battery Voltage has gone above maximum alarm limit
 
61 
BAT VOLT LO ALRM   
Battery Voltage has gone below minimum alarm limit
 
62 
BAT VOLT HI WARN   
Battery Voltage has gone above maximum warning limit
Appendix B
H-100 Control Panel Technical Manual