SJ300 Inverter
Appendix B
B–11
Command – 05
The 05 command reads the inverter’s trip history. 
The frame format of command 05 follows the 
diagrams and specification tables. The transmit 
frame has no data field.
The receive frame has a 440-byte data field. This 
consists of an 8-byte total accumulated number of 
trip events, followed by six 72-byte strings for the 
six most recent trip events as shown below.
The nine bytes of data for each trip event history is listed below. The data contains the multi-
plier to adjust the decimal point. Divide the data by that factor to derive the actual value.
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
Command
Transmission command
2 bytes 05
BCC
Block check sum code
2 bytes Exclusive OR of Node, 
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
Element
Description
Size
Value
STX
Control code (STart of TeXt)
1 byte
STX (0x02)
Node
Node (station) address of inverter
2 bytes 01 to 32
Data
Transmission data
440 
bytes
(see next table)
BCC
Block check sum code
2 bytes Exclusive OR of Node, 
Command, and Data
[CR]
Control code (carriage return)
1 byte
[CR] (0x0D)
No.
Monitor Item
Units
Multiplier
1
Trip  factor
2
Inverter Status A
3
Inverter Status B
4
Inverter Status C
5
Output frequency
Hz
10
6
Accumulated Run Mode time
hours
1
7
Output current
A
10
8
Output voltage
V
10
9
Power ON time
hours
1
STX Node
Command
BCC [CR]
Transmit frame format
STX Node
Data
BCC [CR]
Receive frame format
Data field contents
Trip 3
Trip 2
Trip 1
Total count
Trip 6
Trip 5
Trip 4