Pulse Train Input Operation
 
The WJ200 inverter is capable of accepting pulse train input signals, that are used for 
frequency command, process variable (feedback) for PID control, and simple positioning. 
The dedicated terminal is called “EA” and “EB”. Terminal “EA” is a dedicated terminal, and 
the terminal “EB” is an intelligent terminal, that has to be changed by a parameter setting. 
 
 
 
 
 
 
 
 
Terminal Name 
Description 
Ratings 
EA 
Pulse train input A 
For frequency command, 32kHz max. 
Reference voltage: Common is [L] 
EB 
(Input terminal 7) 
Pulse train input B 
(Set 
C007
 to 
85
 ) 
27Vdc max. 
For frequency command, 2kHz max. 
Reference voltage: Common is [PLC] 
 
(1) Frequency Command by pulse train input 
When using this mode, you should set 
A001
 to 
06
. In this case the frequency is detected by 
input-capture, and calculated based on the ratio of designated max. frequency (under 
32kHz). Only an input terminal “EA” will be used in this case. 
(2) Using for process variable of PID control 
You can use the pulse train input for process variable (feedback) of PID control. In this 
case you need to set 
A076
 to 
03
. Only “EA” input terminal is to be used. 
(3) Simple positioning by pulse train input 
This is to use the pulse train input like an encoder signal. You can select three types of 
operation.
   
   