Installation of Optional Modules
Installation
MS-2/MS-4   PN 51512:E  01/18/05
27
2.6.2  4XTMF, 4XLMF and 4XZMF Option Modules
MS-4:  The 4XLMF LED Interface Module can only be plugged into connectors J3 and 
J5 on the MS-4 main circuit board.  The  4XTMF and 4XZMF modules can be plugged 
into connectors J3 and J5 or J4 and J6 on the MS-4 main circuit board.  A combination 
of any two of the three modules can be installed.  
MS-2:  Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2 
main circuit board. (No other option modules can be installed on the MS-2). 
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) 
on the main circuit board to allow the control panel to supervise the placement of 
any installed option module
3. Install the two supplied metal standoffs in the locations indicated.  These 
standoffs provide the required earth ground protection
4. Carefully plug the connectors on the option module into connectors J3 and J5 or 
J4 and J6 on the FACP main circuit board, being careful not to bend any pins 
5. Secure the option module to the standoff on the main circuit board with the 
supplied screws
6. When the installation has been completed, connect the wiring to the modules as 
indicated in the following sections
7. Test system for proper operation
ON
12
3
4
5
6
78
ON
12
3
4
5
6
78
ON
12
3
4
5
6
78
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK
TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WALK
TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB
1
TB
2
TB3
TB
5
TB
6
TB
7
J1
B+   B-     B+    B-
  NAC 1    NAC 2
 +     -     +     -
Nonreset   Reset
B+    B-    B+    B-
 ZONE 1  ZONE 2
B+    B-    B+    B-
 ZONE 3  ZONE 4
C  TRBL NORM
    TROUBLE
C     NC   NO
ALARM
SUPV
C     NC   NO
J3
J5
J4
J8
J7
J9
TB8
J6
JP1
JP3
SW1
BATTERY
HOT NEUT EARTH
T
R
AN
SF
O
R
M
E
R
 1
T
R
AN
SF
O
R
M
E
R
 2
SW2 SW3
JP2
EARTH BATT CHG
CLASS A
CONVERTER
Figure 2.12 4X Option Module Connection to MS-4
J3
J5
J4
J6
JP1 Jumper
Cut to install 
module on J3 & J5
JP2 Jumper
Cut to install module on J4 & J6
Standoffs
(when using 
J3 & J5
ms4
bor
d.cdr
Standoffs
(when using 
J4 & J6