Honeywell MS-2 Manual Do Utilizador

Página de 56
Installation
Installation of Optional Modules
26
MS-2/MS-4   PN 51512:E  01/18/05
2.6.1.2  Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the MS-4 
and TB1 of the CAC-4 module.  Wire the Style D (Class A) Initiating Device 
Circuits using TB3 of the MS-4 and TB1 of the CAC-4.  Make certain to observe 
polarity when connecting the devices to the circuits.  The B+ and A+ terminals must 
comprise the feed and return for the positive side of a device and the B- and A- 
terminals must comprise the feed and return for the negative side of a device.  To 
configure any of the zones for Class B when the CAC-4 is installed, simply wire to 
the B+ and B- input on the FACP terminal(s) and install the End-of-Line Resistor 
after the last device on the circuit.  Do not wire to the corresponding A+ and A- 
terminals on the CAC-4 module.  Note that Zone 1 IDC on the MS-2 and Zone 2 
IDC on the MS-4 can be configured as a combination waterflow/supervisory circuit 
as illustrated in the following figure.
TB
3
TB
2
B+   B-     B+    B-
  NAC 1    NAC 2
B+    B-    B+    B-
 ZONE 1  ZONE 2
B+    B-    B+    B-
 ZONE 3  ZONE 4
TB
1
A+    A-     A+     A-
NAC 1      NAC 2
CLASS A  CLASS A
A+    A-     A+     A-
ZONE 1    ZONE 2
CLASS A  CLASS A
A+    A-     A+     A-
ZONE 3    ZONE 4
CLASS A  CLASS A
Figure 2.11 Wiring NACs and IDCs for Class A Operation
CAC-4 Class A Converter Module
MS-4 
Circuit Board
Class B (Style B) 
IDC - 4.7 K
Ω
½ watt ELR 
resistor
P/N:71252 
(supervised and 
power-limited)
Dummy load all unused 
circuits - 4.7 K
Ω
½ watt ELR resistor 
(P/N: 71245)
Polarized
Bell
Circuit polarities 
shown in alarm 
condition
Class A (Style Z) NAC 
(supervised and power-limited)
Class A 
(Style D) IDC 
(supervised and 
power-limited)
Class A 
(Style D) IDC
Combo Waterflow 
& Supervisory
20K
Ω, ½ watt ELR 
resistor P/N:75477 
(supervised and 
power-limited)
1.2 K
Ω
½ watt
In-Line
 resistor
P/N:75579
Polarized
Strobe
Polarized
Horn
Tamper
Tamper
Waterflow
Smoke
Smoke
Pull Station
Pull Station
Heat
Heat
IMPORTANT!  
All devices must be 
within 20 feet of the 
Class A portion of 
the circuit and 
wiring must be in 
conduit.
ms
4c
omba.cdr