Unusual diagnosis 
 
7.1.  Option error 
The error message is displayed when there is hardware error, software error or lose of   
connection of wire.
 
 
Display of trip information
 
e
-
23
 (Optional unit fault 2 : 0037H) : Option error
 
 
7.2.  Disconnection error of network cable 
▼Display of trip information 
err8
 (
Optional unit fault 1
: 001BH): 
Network error stop
 
*If a network error occurs when c101 is set to "4", it is displayed. 
 
Related parameter
 
Title Function Setting 
range 
Description 
c100 
Communication error   
detection delay time
 
0.0 to100.0 sec
 
The waiting time from when a network error occurs 
can be adjusted. If a network error continues past the 
time set in c100, it is recognized as a 
communication error and the operation of the inverter 
follows the setting of c101. 
When normal communication returns during the 
setting time, a communication error is not displayed 
and operation is continued. 
 
*
 Time-out time
 = CC-Link network time out 
+ c100 
(communication error detection delay time) [0.1s]
 
c101 
Inverter operation at the 
communications loss action 
0 to 5 
The operation of the drive when the communication 
fault occurs can be specified.
 
c102 
Preset speed operation 
selection 
0 to 15 
The operation frequency of the drive when the 
communication fault occurs can be specified. (Only 
when c101 is set to 5) 
c103 
Communication time-out 
condition selection 
0 to 2 
Select the communication time-out condition.