Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
10.  EMC 
This redundancy module is suitable for applications in industrial environment as well as in residential, commercial and 
light industry environment without any restrictions (e.g. cable length). The CE mark indicates conformance with EMC 
directive 2004/108/EC and the low-voltage directive (LVD) 2006/95/EC. 
A detailed EMC report is available on request. 
 
EMC Immunity 
According generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
Contact discharge 
Air discharge 
8kV 
15kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
Input 
lines 
Output lines 
Alarm contacts 
2kV 
2kV 
2kV 
Criterion A 
Criterion A 
Criterion A 
Surge voltage on  
input lines 
EN 61000-4-5 
+ Æ - 
+/- Æ Chassis ground 
200V 
1kV  
Criterion A 
Criterion A 
Surge voltage on  
output lines 
EN 61000-4-5 
+ Æ - 
+/- Æ Chassis ground 
200V 
1kV 
Criterion A 
Criterion A 
Surge voltage on  
alarm contacts 
EN 61000-4-5 
Alarm contact Æ Chassis ground 
1kV 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
Power-frequency magnetic 
field *) 
EN 61000-4-8 
50Hz 
30A/m 
Criterion A 
Criterions: 
A:    Redundancy module shows normal operation behavior within the defined limits. 
Notes: 
*)    A test is not applicable according to EN 61000-6-2, since the device does not contain components susceptible to magnetic fields, e.g. hall  
elements, electrodynamic microphones, etc. 
 
 
EMC Emission 
According generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
Class B, input lines *) 
 
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1 
Class B, output lines *) 
Radiated emission 
EN 55011, EN 55022 
Class B 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
*) 
Provided, that power sources connected on the inputs fulfill the class B requirements too. 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
8/18