YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
11.  E
NVIRONMENT
 
 
Operational temperature 
*)
 
-40°C to +70°C (-40°F to 158°F) 
Reduce output power above +60°C 
Output de-rating 
0.5A/°C 
60-70°C   (140°F to 158°F), see 
Storage temperature 
-40 to +85°C  (-40°F to 185°F) 
for storage and transportation 
Humidity 
**)
 
5 to 95% r.H. 
IEC 60068-2-30 
Vibration sinusoidal 
2-17.8Hz: ±1.6mm 
17.8-500Hz: 1g 
2 hours / axis 
IEC 60068-2-6 
Shock 
30g 6ms, 20g 11ms 
3 bumps / direction 
18 bumps in total 
IEC 60068-2-27 
Altitude 
0 to 6000m  (0 to 6 560ft) 
without any restrictions 
 
2000 to 6000m  (6 560 to 20 000ft) 
reduce output power or ambient temperature, 
see Fig. 11-2
 
Altitude de-rating 
1.25A/1000m or 5°C/1000m 
> 2000m (6500ft), see Fig. 11-2
Over-voltage category 
not applicable 
The concept of the overvoltage category is 
used for equipment energized directly from 
the low voltage mains (IEC 60664-1 §4.3.3.2.1). 
Degree of pollution 
IEC 62103, EN 50178, not conductive 
*)   Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. 
**)   Do not energize while condensation is present 
 
 
Fig. 11-1   Output current vs. ambient temp. 
 
Fig. 11-2   Output current vs. altitude 
 
Allowed Output  Current
0
-40
0
20
40
70°C
5
10
15
20
25
30A
60
-25
normal mode
at overload / short circuit
Ambient Temperature
 
 
Allowed Output Current
0
0
2000
4000
6000m
5
10
15
20
25
30A
normal mode
Altitude
overload / short circuit
A... Tamb < 60°C
B... Tamb < 50°C
C... Tamb < 40°C
A
B
C
 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 