Puls YRM2.DIODE Redundancy Module Guia De Especificação

Página de 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
6.  R
ELIABILITY
 
 
The redundancy module does not have electrolytic capacitors included. Therefore, the lifetime expectancy and MTBF 
value is extremely high. 
Input / output  
current conditions 
 
Input: 2x10A
Output: 20A 
Input: 2x5A 
Output: 10A 
 
Lifetime expectancy 
*)
 
min. 
25 years 
25 years 
at 24V and 40°C 
 
min. 
25 years 
25 years 
at 24V and 25°C 
MTBF 
**)
  SN 29500, IEC 61709 
 
9 100 000h 
10 900 000h 
at 24V 40°C 
 
 
15 700 000h 
18 800 000h 
at 24V 25°C 
MTBF 
**)
  MIL HDBK 217F 
 
9 200 000h 
11 100 000h 
at 24Vand 40°C (Ground Benign GB40) 
 
 
12 600 000h 
15 100 000h 
at 24Vand 25°C (Ground Benign GB25) 
 
 
3 380 000h 
4 060 000h 
at 24Vand 40°C (Ground Fixed GF40) 
 
 
4 630 000h 
5 570 000h 
at 24Vand 25°C (Ground Fixed GF25) 
*)   The Lifetime expectancy shown in the table indicates the minimum operating hours (service life). 
**)  MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a 
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 
 
 
7.  T
ERMINALS AND 
W
IRING
 
 
 
Input and output terminals 
Alarm-signal terminals 
Type Screw 
terminals 
IP20 Finger safe construction. 
Suitable for field installation. 
Screw terminals, pluggable 
IP20 Finger safe construction. 
Suitable for field installation. 
Solid wire 
0.5-6mm
2
 0.2-1.5mm
2
 
Stranded wire 
0.5-4mm
2
 0.2-1.5mm
2
 
American Wire Gauge 
20-10 AWG 
22-14 AWG 
Wire stripping length 
7mm / 0.28inch 
6mm / 0.25inch 
Screwdriver 
3.5mm slotted or Pozidrive No 2 
3mm slotted 
Recommended tightening torque 
0.8Nm / 7lb.in 
0.4Nm / 3.5lb.in 
Instructions: 
a)  The external circuitry of all terminals (including signalling contacts) must meet the safety requirements stipulated by 
IEC/EN/UL 60950-1: SELV. 
b)  Use appropriate copper cables that are designed for minimum operating temperatures of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum. 
c)  Follow national installation codes and installation regulations! 
d)  Ensure that all strands of a stranded wire enter the terminal connection! 
e)  Up to two stranded wires with the same cross section are permitted in one connection point. 
f)  Screws of unused terminal compartments should be securely tightened. 
g)  Ferrules are allowed, but not required. 
h)  Do not connect or disconnect the wires from the terminals below -25°C (-13°F).
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 
www.pulspower.com   Phone +49 89 9278 0    Germany 
6/18