Puls ML50.100 Power Supply Guia De Especificação

Página de 20
 
 
 
ML50.100, ML50.109 
 
MiniLine 
 
24V, 2.1A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
13/20 
 
21. A
PPROVALS
 
 
 IEC 
60950-1 
IECEE
 
CB SCHEME 
CB Scheme,  
Information Technology Equipment 
 IEC 
60601-1 
IECEE
 
CB SCHEME 
CB Scheme,  
Medical,  Basic Insulation 
 UL 
508 
IND. CONT. EQ.
 
LISTED as Industrial Control Equipment  E198865
 
 UL2601 
 
LISTED as Medical
 
 UL 
60950-1 
 
RECOGNIZED   E137006   recognized for the use in U.S.A. (UL 60950-1) and Canada 
(C22.2 No. 60950).  Information Technology Equipment, Level 3  
  NEC Class 2 
 
Listed as Limited Power Source (LPS) in the UL 60950-1 UL report. 
 UL 
1604 
 
RECOGNIZED   E246877    recognized for use in U.S.A. (UL 1604) and Canada (C22.2 
No. 213-M1987) Hazardous Location Class I Div 2 T4 Groups A,B,C,D and  
Class I Zone 2 Groups IIA, IIB and IIC 
   
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I Zone 2 
Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for Class I Division 2 
environment. Do not disconnect equipment unless power has been switched off. Wiring must be in 
accordance with Class I, Division 2 wiring methods of the National Electrical Code, NFPA 70, and in 
accordance with other local or national codes. 
 Marine 
GL
  
ABS
 
GL (Germanischer Lloyd) classified and ABS (American Bureau for Shipping) PDA 
for marine and offshore applications. Environmental category: C, EMC2 
 SEMI 
F47 
 
SEMI F47-0200 Power Quality Star 
Ride-through compliance for semiconductor industry. 
Full SEMI range compliance (Input: 120Vac or 208Vac) 
 
22. F
ULFILLED 
S
TANDARDS
 
 
  EN 61558-2-17 
Safety of Power Transformers 
  EN/IEC 60204-1 
Safety of Electrical Equipment of Machines 
  EN/IEC 61131-2 
Programmable Controllers 
  EN 50178, IEC 62103 
Electronic Equipment in Power Installations 
 
23. U
SED 
S
UBSTANCES
 
 
  Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. 
  Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated. 
  The unit conforms to the RoHS directive 2002/96/EC 
 
The materials used in our production process do not include the following toxic chemicals: 
Polychlorinated Biphenyl (PCB), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrominated  
Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE), Polychlorinated 
Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxide (PBDO), Cadmium, Asbestos, Mercury, Silica