Puls ML60.241 Power Supply Guia De Especificação

Página de 22
 
 
ML60.241
 
 
MiniLine 
 
24V,
 
2.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
13.  EMC 
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. The CE mark indicates conformance with EMC directive 2004/108/EC 
and the low-voltage directive (LVD) 2006/95/EC. A detailed EMC report is available on request. 
 
EMC Immunity 
Generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
Contact discharge 
Air discharge 
8kV 
8kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
Input 
lines 
Output lines 
4kV 
2kV 
Criterion A 
Criterion A 
Surge voltage on input 
EN 61000-4-5 
L Æ N 
N Æ PE, L Æ PE 
2kV 
4kV 
Criterion A 
Criterion A 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ Æ PE, - Æ PE 
1kV 
2kV 
Criterion A 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
Mains voltage dips 
EN 61000-4-11 
0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac
 
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A *) 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 
Voltage interruptions 
EN 61000-4-11 
 
0Vac, 5000ms 
Criterion C 
Input voltage swells 
PULS internal standard 
300Vac, 500ms 
Criterion A 
Powerful transients 
VDE 0160 
over entire load range 
750V, 1.3ms 
Criterion A 
Criterions: 
A:    Power supply shows normal operation behavior within the defined limits. 
B: 
The power supply operates continuously during and after the test. During the test minor temporary impairments may occur, which will be 
corrected by the power supply itself. 
C:    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 
will occur. 
*) 
Up to 2A output current criterion A, above 2A output current criterion B
 
 
EMC Emission 
Generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 
Class B, input lines 
Radiated emission 
EN 55011, EN 55022, CISPR 11, CISPR 22 
Class B 
Harmonic input current 
EN 61000-3-2 
Not applicable below 75W 
input power 
Voltage fluctuations, 
flicker *) 
EN 61000-3-3 
Fulfilled 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
*) tested with constant current loads, non pulsing 
 
 
Switching frequency 
 
 
Converter frequency 
variable, typ. 100kHz, min. 45kHz, max. 160kHz 
Input voltage and output 
load dependent 
Sep. 2010 / Rev. 1.0  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
11/22