Puls ML60.241 Power Supply Guia De Especificação

Página de 22
 
 
ML60.241
 
 
MiniLine 
 
24V,
 
2.5A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
5.  O
UTPUT
 
 
Output voltage 
nom. 
24V 
 
Adjustment range 
min. 
24-28V 
guaranteed 
 
max. 
30V *) 
at clockwise end position of potentiometer 
Factory setting 
 
24.5V  
 ±0.2%, at full load, cold unit 
Line regulation 
max. 
10mV 
85-264Vac 
Load regulation 
max. 
100mV 
static value, 0A Æ 2.5A 
Ripple and noise voltage 
max. 
50mVpp 
20Hz to 20MHz, 50Ohm 
Output capacitance 
typ. 
1 600μF 
 
Output current  
nom. 
2.5A 
at 24V, see Fig. 5-1
 
 
nom. 
2.1A 
at 28V, see Fig. 5-1
 
Output power 
nom. 
60W 
 
Short-circuit current 
min. 
3.6A 
 
max. 
6.2A 
*) 
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not 
guaranteed value which can be achieved. The typical value is about 28.6V. 
 
 
Fig. 5-1   Output voltage vs. output current, 
typ. 
 
 
 
Output Voltage
0
0
4
8
12
28V
16
20
24
3
2
1
5
6A
4
Adjustment
Range
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
 
 
 
 
 
Peak current capability (up to several milliseconds) 
The power supply can deliver a peak current which is higher than the specified short term current. This helps to start 
current demanding loads or to safely operate subsequent circuit breakers. 
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be 
discharged and causes a voltage dip on the output. Detailed curves can be found in chapter 23.1
Peak current voltage dips  
typ. 
from 24V to 16V 
at 5A for 50ms, resistive load 
 
typ. 
from 24V to 15V 
at 12.5A for 2ms, resistive load 
 
typ. 
from 24V to 10.5V 
at 12.5A for 5ms, resistive load 
 
Sep. 2010 / Rev. 1.0  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
6/22