Puls QS20.241 Power Supply Guia De Especificação

Página de 26
 
 
QS20.241, QS20.241-A1, QS20.241-C1
 
 
Q-Series 
24V,
 
20A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
10.  L
IFETIME 
E
XPECTANCY AND 
MTBF 
 
 AC 
100V 
AC 120V 
AC 230V 
 
Lifetime expectancy 
*)
 
54 000h 
59 000h 
71 000h 
at 24V, 20A and 40°C 
 
135 000h 
143 000h 
164 000h 
at 24V, 10A and 40°C 
 
153 000h *) 
165 000h *) 
200 000h *) 
at 24V, 20A and 25°C 
MTBF 
**)
  SN 29500, IEC 61709 
407 000h 
441 000h 
469 000h 
at 24V, 20A and 40°C 
 
749 000h 
799 000h 
840 000h 
at 24V, 20A and 25°C 
MTBF 
**)
  MIL HDBK 217F 
204 000h 
215 000h 
229 000h 
at 24V, 20A and 40°C; Ground 
Benign GB40 
 
273 000h 
288 000h 
308 000h 
at 24V, 20A and 25°C; Ground 
Benign GB25 
*)   The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the 
capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices. 
**)  MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a 
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 
 
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 
has been running for 50 000h or only for 100h. 
 
 
 
11.  F
UNCTIONAL 
D
IAGRAM
 
 
 
Fig. 11-1   Functional diagram 
 
 
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter
Output
Voltage
Regulator
Power
Converter
Output
Filter
DC-ok
Relay
Output
Voltage
Monitor
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Active Inrush Limiter
V
OUT
L
N
DC-ok
Contact
Overload
LED
DC-ok
LED
 
 
 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 