Puls QS20.241 Power Supply Guia De Especificação

Página de 26
 
 
QS20.241, QS20.241-A1, QS20.241-C1
 
 
Q-Series 
24V,
 
20A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
9.  E
FFICIENCY AND 
P
OWER 
L
OSSES
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Efficiency  
typ. 
91.6% 
92.4% 
93.9% 
at 24V, 20A 
Average efficiency *) 
typ. 
91.0% 
91.8% 
92.9% 
25% at 5A, 25% at 10A, 25% 
at 15A. 25% at 20A 
Power losses 
typ. 
9.0W 
9.2W 
10.0W 
at 24V, 0A 
 
typ. 
44.0W 
39.6W 
31.4W 
at 24V, 20A 
*)   The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25% 
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100% 
of the nominal load for the rest of the time. 
 
 
 
Fig. 9-1 
Efficiency vs. output current at 24V, 
typ 
 
Fig. 9-2  Losses vs. output current at 24V, typ.  
 
Efficiency
4
6
8
10
12
14
16
18 20A
86
87
88
89
90
91
Output Current
92
93
94%
120Vac
100Vac
230Vac
 
 
Power Losses
0
2
4
6
8 10 12 14
20A
10
5
20
25
30
40
45W
120Vac
100Vac
230Vac
16 18
35
15
Output Current
 
 
Fig. 9-3 
Efficiency vs. input voltage at 24V, 
20A, typ. 
 
Fig. 9-4  Losses vs. input voltage at 24V, 20A, 
typ. 
 
Efficiency
85
120
155
190
225 260Vac
88
89
90
91
Input Voltage
92
93
94%
 
 
Power Losses
20
25
30
35
40
45
50W
85
120
155
190
225 260Vac
Input Voltage
 
Oct. 2013 / Rev. 2.2 DS-QS20.241-EN 
All parameters are specified at 24V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 