Puls ML15.121 Power Supply Guia De Especificação

Página de 23
 
 
ML15.121
 
 
MiniLine-2 
 
12V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
11.  T
ERMINALS AND 
W
IRING
 
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each 
other (input below, output above) to help in error-free wiring. 
 
 
Input Output 
 
Type 
screw terminals 
screw terminals 
 
Solid wire 
0.5-6mm
2
 0.5-6mm
2
 
 
Stranded wire 
0.5-4mm
2
 0.5-4mm
2
 
 
American Wire Gauge 
20-10 AWG 
20-10 AWG 
 
Wire stripping length 
7mm / 0.275inch 
7mm / 0.275inch 
 
Screwdriver 
3.5mm slotted or 
Pozidrive No 2 
3.5mm slotted or 
Pozidrive No 2 
 
Recommended tightening torque 
1Nm, 9lb.in 
1Nm, 9lb.in 
 
Instructions: 
a)  Use appropriate copper cables that are designed for minimum operating temperatures of:  
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.  
b) Follow
 national installation codes and installation regulations! 
c)  Ensure that all strands of a stranded wire enter the terminal connection!  
d)  Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire). 
e)  Do not use the unit without PE connection. 
f)  Screws of unused terminal compartments should be securely tightened. 
g)  Ferrules are allowed. 
 
 
 
12.  L
IFETIME 
E
XPECTANCY AND 
MTBF 
These units are extremely reliable and use only the highest quality materials. The number of critical components such 
as electrolytic capacitors has been reduced. 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Lifetime expectancy 
*)
 
123 000h 
126 000h 
125 000h 
at 12V, 1.3A and 40°C 
 
> 15 years 
> 15 years 
> 15 years 
at 12V, 0.65A and 40°C 
 
> 15 years 
> 15 years 
> 15 years 
at 12V, 1.3A and 25°C 
MTBF 
**)
 SN 29500, IEC 61709  3 435 000h 
3 723 000h 
3 811 000h 
at 12V, 1.3A and 40°C 
 
5 633 000h 
6 106 000h 
6 205 000h 
at 12V, 1.3A and 25°C 
MTBF 
**)
 MIL HDBK 217F 
1 482 000h 
1 534 000h 
1 451 000h 
at 12V, 1.3A and 40°C; Ground Benign GB40 
 
1 986 000h 
2 056 000h 
1 944 000h 
at 12V, 1.3A and 25°C; Ground Benign GB25 
*)   The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime 
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the 
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment. 
**)  MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a 
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 
 
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that 
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit 
has been running for 50 000h or only for 100h. 
Mar. 2013 / Rev. 2.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 