Puls ML15.121 Power Supply Guia De Especificação
ML15.121
MiniLine-2
12V,
1.3A,
S
INGLE
P
HASE
I
NPUT
11. T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.
other (input below, output above) to help in error-free wiring.
Input Output
Type
screw terminals
screw terminals
Solid wire
0.5-6mm
2
0.5-6mm
2
Stranded wire
0.5-4mm
2
0.5-4mm
2
American Wire Gauge
20-10 AWG
20-10 AWG
Wire stripping length
7mm / 0.275inch
7mm / 0.275inch
Screwdriver
3.5mm slotted or
Pozidrive No 2
Pozidrive No 2
3.5mm slotted or
Pozidrive No 2
Pozidrive No 2
Recommended tightening torque
1Nm, 9lb.in
1Nm, 9lb.in
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b) Follow
national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed.
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed.
12. L
IFETIME
E
XPECTANCY AND
MTBF
These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.
as electrolytic capacitors has been reduced.
AC 100V
AC 120V
AC 230V
Lifetime expectancy
*)
123 000h
126 000h
125 000h
at 12V, 1.3A and 40°C
> 15 years
> 15 years
> 15 years
at 12V, 0.65A and 40°C
> 15 years
> 15 years
> 15 years
at 12V, 1.3A and 25°C
MTBF
**)
SN 29500, IEC 61709 3 435 000h
3 723 000h
3 811 000h
at 12V, 1.3A and 40°C
5 633 000h
6 106 000h
6 205 000h
at 12V, 1.3A and 25°C
MTBF
**)
MIL HDBK 217F
1 482 000h
1 534 000h
1 451 000h
at 12V, 1.3A and 40°C; Ground Benign GB40
1 986 000h
2 056 000h
1 944 000h
at 12V, 1.3A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit
has been running for 50 000h or only for 100h.
Mar. 2013 / Rev. 2.1 DS-ML15.121-EN
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/23