Puls ML15.121 Power Supply Guia De Especificação

Página de 23
 
 
ML15.121
 
 
MiniLine-2 
 
12V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
13.  EMC 
The power supply is suitable for applications in industrial environment as well as in residential, commercial and light 
industry environment without any restrictions. A detailed EMC report is available on request. 
 
EMC Immunity 
Generic standards: EN 61000-6-1 and EN 61000-6-2 
Electrostatic discharge  
EN 61000-4-2 
Contact discharge 
Air discharge 
8kV 
8kV 
Criterion A 
Criterion A 
Electromagnetic RF field 
EN 61000-4-3 
80MHz-2.7GHz 
10V/m 
Criterion A 
Fast transients (Burst) EN 
61000-4-4 
Input 
lines 
Output lines 
4kV 
2kV 
Criterion A 
Criterion A 
Surge voltage on input 
EN 61000-4-5 
L Æ N 
N Æ PE, L Æ PE 
2kV 
4kV 
Criterion A 
Criterion A 
Surge voltage on output 
EN 61000-4-5 
+ Æ - 
+ Æ PE, - Æ PE 
500V 
2kV 
Criterion A 
Criterion A 
Conducted disturbance 
EN 61000-4-6 0.15-80MHz 
10V 
Criterion 
Mains voltage dips 
EN 61000-4-11 
0% of 100Vac 
40% of 100Vac 
70% of 100Vac 
0% of 200Vac
 
40% of 200Vac 
70% of 200Vac 
0Vac, 20ms 
40Vac, 200ms 
70Vac, 500ms 
0Vac, 20ms 
80Vac, 200ms 
140Vac, 500ms 
Criterion A 
Criterion C  
Criterion A 
Criterion A 
Criterion A 
Criterion A 
Voltage interruptions 
EN 61000-4-11 
 
0Vac, 5000ms 
Criterion C 
Input voltage swells 
PULS internal standard 
300Vac, 500ms 
Criterion A 
Powerful transients 
VDE 0160 
over entire load range 
750V, 1.3ms 
Criterion A 
Criterions: 
A:    Power supply shows normal operation behavior within the defined limits.  
C:    Temporary loss of function is possible. Power supply may shut-down and restarts by itself. No damage or hazards for the power supply 
will occur. 
 
EMC Emission 
Generic standards: EN 61000-6-3 and EN 61000-6-4 
Conducted emission  
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22 
Class B, input lines 
Radiated emission 
EN 55011, EN 55022 
Class B 
Harmonic input current 
EN 61000-3-2 
Not applicable below 75W 
input power 
Voltage fluctuations, flicker EN 
61000-3-3 
fulfilled 
This device complies with FCC Part 15 rules. 
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this 
device must accept any interference received, including interference that may cause undesired operation. 
 
Switching frequency 
Constant, typ. 65kHz 
 
Mar. 2013 / Rev. 2.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 