Puls ML15.121 Power Supply Guia De Especificação

Página de 23
 
 
ML15.121
 
 
MiniLine-2 
 
12V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
4.  DC-I
NPUT
 
 
DC input 
nom. 
DC 110-300V 
-20%/+25% 
DC input range 
min. 
88-375Vdc 
continuous operation 
DC input current 
typ. 
0.16A / 0.057A 
110Vdc / 300Vdc, at 12V, 1.3A 
Turn-on voltage 
typ. 
80Vdc 
steady state value 
Shut-down voltage 
typ. 
60Vdc 
steady state value 
 
 
Fig. 4-1   Wiring for DC Input 
 
Instructions for DC use: 
 
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
 
 
a)  Use a battery or similar DC source. 
For other sources contact PULS 
b)  Connect +pole to L and –pole to N. 
c)  Connect the PE terminal to an earth wire or to the 
machine ground. 
 
 
5.  I
NPUT 
I
NRUSH 
C
URRENT
 
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and 
ambient temperature dependent. 
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on. 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Inrush current 
max. 
13A
peak
 16A
peak
 31A
peak
 
40°C ambient, cold start 
 typ. 
11A
peak
 13A
peak
 26A
peak
 
40°C ambient, cold start 
Inrush energy 
max. 
0.1A
2
s 0.1A
2
s 0.4A
2
40°C ambient, cold start 
 
 
Fig. 5-1   Input inrush current, typical behavior 
 
Fig. 5-2   Input inrush current, zoom into first peak 
 
 
Input Voltage
Input Current
 
 
Input Current
 
 
 
 
Input:  
230Vac 
Output:  
12V, 1.3A 
Ambient: 25°C 
Upper curve: 
Input current 5A/DIV 
Lower curve: 
Input voltage 500V/DIV 
Time basis:  
10ms / DIV 
 
Input:  
230Vac 
Output:  
12V, 1.3A 
Ambient: 25°C 
Input current curve: 5A/DIV, 500μs / DIV 
Ipeak 23A 
 
Mar. 2013 / Rev. 2.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
5/23