Puls ML15.121 Power Supply Guia De Especificação
ML15.121
MiniLine-2
12V,
1.3A,
S
INGLE
P
HASE
I
NPUT
7. H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
62ms
96ms
365ms
at 12V, 0.65A, see Fig. 7-1
typ.
30ms
46ms
191ms
at 12V, 1.3A, see Fig. 7-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time
Fig. 7-1 Hold-up time vs. input voltage
Fig. 7-2 Shut-down behavior, definitions
0
25
50
125
150ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
75
100
a) 12V 0.65A typ.
b) 12V 0.65Amin.
c) 12V 1.3A typ.
d) 12V 1.3A min.
b) 12V 0.65Amin.
c) 12V 1.3A typ.
d) 12V 1.3A min.
a
b
c
d
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Voltage
Input
Voltage
Voltage
Mar. 2013 / Rev. 2.1 DS-ML15.121-EN
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
7/23