Puls ML15.121 Power Supply Guia De Especificação

Página de 23
 
 
ML15.121
 
 
MiniLine-2 
 
12V,
 
1.3A,
 
S
INGLE 
P
HASE 
I
NPUT
 
 
 
7.  H
OLD
-
UP 
T
IME
 
 
 
 
AC 100V 
AC 120V 
AC 230V 
 
Hold-up Time 
typ. 
62ms 
96ms 
365ms 
at 12V, 0.65A, see Fig. 7-1
 
typ. 
30ms 
46ms 
191ms 
at 12V, 1.3A, see Fig. 7-1
 
Note:  At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time 
 
 
 
Fig. 7-1   Hold-up time vs. input voltage 
 
Fig. 7-2   Shut-down behavior, definitions 
 
0
25
50
125
150ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
75
100
a) 12V 0.65A typ.
b) 12V 0.65Amin.
c) 12V 1.3A typ.
d) 12V 1.3A min.
a
b
c
d
 
 
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
 
 
Mar. 2013 / Rev. 2.1  DS-ML15.121-EN 
All parameters are specified at 12V, 1.3A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 