Baicells Technologies Co. Ltd. MBS1105 Manual Do Utilizador

Página de 31
Baicells mBS1105 Base Station Installation Guide(V100R001C00,02).docx 
 
 
Installation Environment 
3.3
3.3.1  Locational Requirements 
Environments  with  high-temperatures,  harmful  gases,  unstable  voltages,  volatile 
vibrations, loud noises, flames, explosives, and electromagnetic interference (large radar 
stations, transmitting stations, transformer substations) are not suitable for the operation 
of mBS1105, and thus should be avoided.   
Places prone to have impounded water, soaking, leakage, or condensation, should also 
be avoided.   
Factors like climate, hydrology, geology, earthquake, electric power, and transportation 
should be taken into consideration in the construction process so that a proper location 
can be chosen to meet the communication engineering environmental requirements, as 
well as the technical requirements of network planning and communication equipment. 
3.3.2  Environmental Requirements 
the  base  station’s  environmental  requirements  with  regards  to 
temperature, humidity, and voltage.   
Table 3-2 Environmental Requirements of the Base Station 
Item 
Range 
Typical value 
Humidity 
-40℃~ 55℃ 
25℃ 
Relative humidity (no condensation)  0% ~ 100% 
5% ~ 95% 
Safety voltage 
42V ~ 58V 
48V 
 
3.3.3  Space Requirements 
After the eNodeB has installed, the  enough space must be provided for operation and 
maintenance.  And  for  heat  dissipation  and  normal  running  of  the  eNodeB,  the  space 
must be planed before installation, as shown in Figure 3-1.