Honeywell XL 800 SERIES Manual Do Utilizador

Página de 36
Mounting/Dismounting Modules 
Excel 800 
EN1B-0410GE51 R0908A 
 
16
 
Fig. 19. Connecting terminal sockets with bridge 
connector 
NOTE: 
Bridge connectors transmit both communication 
signals and power supply between modules. 
Removing bridge connectors will interrupt the 
transmission of both communication signals and 
power supply between the modules. 
 
Dismounting Sockets 
Disconnecting Sockets 
Release all bridge connectors before removing the 
XCL8010AU Controller Module and/or the terminal sockets 
from the DIN rail. 
 
► 
Press down at the same time both the gray side wings next 
to the red button and then pull the bridge connector out of 
the module. 
 
 
Fig. 20. Releasing bridge connectors 
 
Dismounting Controller/Terminal Sockets 
► 
Insert a screwdriver into the latch on the underside of the 
module and lever the red latch 2–3 mm downwards. The 
module can then be swung away from the rail. 
 
 
Fig. 21. Releasing latch 
 
Mounting/Dismounting Electronic Modules 
Mounting Electronic Modules 
NOTE: 
Electronic modules can be removed from the 
socket or inserted into the sockets without 
switching off the power supply. The behavior of 
connected field devices must be taken into 
consideration. 
 
► 
Make sure that terminal socket und I/O module match. 
► 
Make sure that the red locking mechanism is in the open, 
i.e., left, position. 
► 
Gently push the electronic module onto the terminal socket 
until snug. 
 
 
Fig. 22. Inserting the electronic module 
 
► 
Lock the red locking mechanism by sliding it to the right.