Excel 800 
Mounting/Dismounting Modules 
 15 
EN1B-0410GE51 
R0908A 
Mounting/Dismounting Controller/Sockets 
Mounting Sockets 
NOTE: 
When using both Panel Bus and L
ON
W
ORKS
 Bus 
I/O modules in an Excel 800 System, group both 
Panel Bus modules (light-gray) and L
ON
W
ORKS
 
Bus I/O modules (dark-gray), e.g., on different 
rails. Up to 10 Panel Bus I/O modules can be 
mounted to one side of the XCL8010AU. In total, 
up to 16 Panel Bus I/O modules can be mounted 
to one controller. The XCL8010AU Controller 
Module is mounted on the DIN rail in the same way 
as a terminal socket. 
 
XCL8010AU
LonWorks
BUS
I/O
max. 10
max. 16
max. 10
Panel
BUS I/O
Panel
BUS I/O
Panel
BUS I/O
Panel
BUS I/O
 
Fig. 16. Max. number of Panel Bus I/O modules 
 
XCL8010AU
LonWorks
BUS I/O
LonWorks
BUS
I/O
max. 10
max. 20
max. 10
LonWorks
BUS I/O
LonWorks
BUS I/O
LonWorks
BUS I/O
NOTE: MAX. OF 16 DIGITAL INPUT MODULES MAY BE USED.
 
Fig. 17. Max. number of L
ON
W
ORKS
 Bus I/O modules with 
power supply via XCL8010AU 
 
► 
Angle the terminal socket at the upper edge of the DIN rail 
until it snaps in. 
► 
Swing the terminal socket down and apply gentle force 
until it snaps into position with an audible "click". 
► 
Position XCL8010AU Controller Module and terminal 
sockets flush with one another along the rail. 
► 
If desired, mount stoppers at the ends of the rail to prevent 
sliding. 
 
 
Fig. 18. Mounting terminal sockets 
NOTE: 
Take care to not bend the Omega clamp, which 
serves to establish the electrical contact with the 
DIN rail and which located on the back of the 
terminal socket. 
 
Connecting Sockets 
Controller and terminal sockets on the same DIN rail can be 
connected mechanically and electrically with bridge 
connectors. 
Controller and terminal sockets on different DIN rails must be 
connected using cables. 
 
NOTICE 
Risk of malfunction! 
► 
Wire Panel Bus I/O modules and L
ON
W
ORKS
 Bus 
I/O modules separately. 
► 
When using both Panel Bus and L
ON
W
ORKS
 Bus 
I/O modules in an Excel 800 System, L
ON
W
ORKS
 Bus 
I/O modules must be connected to the XCL8010AU 
Controller Module via LON terminals 11 ─ 14. 
 
Position the bridge connector on terminals 71 ─ 74 of the 
right hand terminal socket or XCL8010AU Controller Module 
and on terminals 75 ─ 78 of the left hand terminal socket or 
XCL8010AU Controller Module. Then press the bridge 
connector down.