Network Communication Settings
The following table lists parameters that configure the inverter’s serial communications 
port. The settings affect how the inverter communicates with a digital operator (such as
SRW–0EX), as well as a ModBus network (for networked inverter applications). The 
settings cannot be edited via the network, in order to ensure network reliability. Refer to 
 for more information on controlling 
and monitoring your inverter from a network.
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
C071 Communication speed 
selection
Three option codes:
04... 4800 bps
05... 9600 bps
06... 19200 bps
06
04
baud
COM BAU    4800
C072 Node allocation
Set the address of the inverter 
on the network. Range is 1 to 
32.
1.
.1
COM ADR    00001
C074 Communication parity 
selection
Three option codes:
00... No parity
01... Even parity
02... Odd parity
00
00
COM PRTY     NON
C075 Communication stop bit 
selection
Range is 1 to 2
1
1
COM STP     1BIT
C076 Communication error 
select
Selects inverter response to 
communications error.
Five options:
00... Trip (error code E60)
01... Decelerate to a stop and 
trip (error code E60)
02... Disable
03... Free run stop (coasting)
04... Decelerate to a stop
02
02
COM ESlct  None
C077 Communication error 
time-out
Sets the communications 
watchdog timer period.
Range is 0.00 to 99.99 sec.
0.00
0.00
sec.
COM ETIM 000.00s
C078 Communication wait 
time
Time the inverter waits after 
receiving a message before it 
transmits.
Range is 0. to 1000. ms
0.
0.
msec.
COM Wait 00000ms