Analog Signal Calibration Settings
The functions in the following table configure the signals for the analog output termi-
nals. Note that these settings do not change the current/voltage or sink/source character-
istics—only the zero and span (scaling) of the signals.
NOTE: When you restore factory default settings, the values will change to those listed 
above. Be sure to manually reconfigure the values for your application, if needed, after 
restoring factory defaults.
“C” Function
Run 
Mode 
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF 
(EU)
–FU 
(USA)
Units
C081 O input span calibration Scale factor between the 
external frequency command 
on terminals L – O (voltage 
input) and the frequency 
output, range is 0.0 to 200.0%
100.0
100.0
%
O-ADJ    0100.0%
C082 OI input span calibra-
tion
Scale factor between the 
external frequency command 
on terminals L – OI (current 
input) and the frequency 
output, range is 0.0 to 200.0%
100.0
100.0
%
OI-ADJ   0100.0%
C085 Thermistor input tuning Range is 0.0 to 200.0%
100.0
100.0
%
PTC Adj  0100.0%
C086 [AM] terminal offset 
tuning
Range is 0.0 to 10.0V
0.0
0.0
V
AM-OFFST 0000.0V