         WARNING:   Test all gas piping
and connections for leaks after install-
ing or servicing. Correct all leaks at
once.
         WARNING:   Never  use  an  open
flame  to  check  for  a  leak. Apply  a
mixture  of  liquid  soap  and water to
all joints. Bubbles forming show  a
leak. Correct  all  leaks  immediately.
         CAUTION:  Make  sure  external
regulator  has  been  installed  be-
tween natural gas  supply  and  heater.
See guidelines  under  Connecting  to
Gas Supply,  page 8.
Figure  8 -Equipment  Shutoff  Valve
Pressure  Testing  Gas  Supply
Piping  System
Test  Pressures  In Excess  Of  1/2
PSIG(3.5kPa)
1. Disconnect   heater   with  its
appliance  main gas valve (control
valve) and equipment  shutoff  valve
from  gas  supply  piping  system.
Pressures  in  excess of  1/2  psig
will  damage  heater  regulator.
2.   Cap   off   open   end   of   gas  pipe
 where  equipment  shutoff  valve
 was connected.
3.   Pressurize  supply  piping  system
by either using compressed air or
opening  propane/LP  supply  valve.
4.   Check   all   joints   of   gas   supply
piping system. Apply mixture of
liquid  soap  and  water  to  gas
joints. Bubbles  forming  show  a
leak.
5.   Correct all leaks immediately.
6.  Reconnect heater and equipment
shutoff valve to gas supply. Check
reconnected  fittings for leaks.
Pressure   Testing   Heater   Gas
Connections
1.  Open  equipment  shutoff   valve
(see  Figure  8).
Figure  9 -Checking  Gas  Joints
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
2.   Open gas supply  valve.
3.  Make sure heater   is in the OFF
     position.
4. Check all joints from equipment
      s h u t o f f   v a l v e   t o   c o n t r o l   v a l v e
(see  Figure 9).
Apply  mixture of liquid soap and
water  to  gas  joints.  Bubbles form-
ing  show  a  leak.
5.   Correct all leaks immediately.
6.     Light heater (see  Operating    Heater,
    page 10 ). Check all other internal
      joints  for  leaks.
7. Turn  off  heater (see To Turn Off
      Gas  to  Appliance, page10 ).
Test Pressures Equal To or Less
Than 1/2 PSIG ( 3.5 kPa )
1. Close equipment shutoff valve
      (see Figure 8).
2.  Pressurize supply piping system
      by either using compressed air or
      opening gas supply tank valve.
3.   Check all joints from gas meter to
      equipment shutoff valve (see Fig-
    ure 9). Apply mixture of liquid
    soap and water to gas joints.
      Bubbles forming show a leak.
4.   Correct all leaks immediately.