concentrIc vent InstallatIon
This appliance is certified for concentric venting with concentric vent 
kit  #9003910105  and  #9006328005.  Follow  instructions  below  for 
proper installations.
KIt coMponents
Each kit is comprised of the following:
  Item 
Description 
Qty.
  Rain Cap 
3 in. 
1
  SDR-26 pipe 
4 in. dia. 
1
  SDR-26 pipe 
2½ in. dia. 
1
  Y Concentric Fitting 
3 in. 
1
  Installation Instructions 
194504 
1
Field  supplied  pipe  and  fittings  are  required  to  complete  the 
installation.
This concentric vent termination kit may be used with 3 inch diameter 
pipe systems.
safetY consIderatIons
Installing and servicing water heating equipment can be hazardous 
due to gas and electrical components. Installation and service of 
the  concentric  vent  termination  requires  ability  equivalent  to  that 
of a qualified installer or service agent, see page 7. All precautions 
in the literature, on tags, and labels attached to the unit must be 
observed. 
Follow all safety codes. Wear safety glasses and work gloves.
fIGure 20.
fIGure 21.
*    dimension 21 1/8 in. may be lengthened to 60 in. maximum.   
    dimension 21 1/8 in. may also be shortened by cutting the  
    pipes, provided in the kit, to 12 in. minimum.
**   dimension  39  will  change  accordingly  as  dimension  
    21 1/8 in. is lengthened or shortened.
Do  not  use  field-supplied  couplings  to  extend  pipes.  Airflow 
restriction will occur and the heater pressure switch may cause 
intermittent operation.
InstallatIon  procedure  1  roof  terMInatIon,    see 
figure 23. 
1.  Determine best location for termination kit.
note:  roof  termination  is  preferred  since  it  is  less 
susceptible  to  damage,  has  reduced  chances  to  intake 
contaminants, and less visible vent vapors.
2.  Cut 1 hole (5 in. diameter)
3.  Partially assemble concentric vent termination kit.  
  a)  Cement  Y  concentric  fitting  to  larger  diameter  kit  
pipe, see Figure 20.
  b)  Cement rain cap to smaller diameter kit pipe, see Figure 22.
fIGure 22.
note:  Instead of cementing the smaller pipe to the rain cap, 
a field-supplied stainless steel screw may be used to secure 
the 2 components together when field disassembly is desired 
for cleaning, see figure 22.
when using alternate screw method, drill clearance hole in 
rain cap and pilot hole in vent pipe for screw size being used.  
failure  to  drill  adequate  holes  may  cause  cracking  of  pvc 
components, allowing combustion products to be recirculated. 
failure to follow this warning could result in personal injury 
or death.
do  not  operate  the  heater  with  rain  cap  removed  or 
recirculation of combustion products may occur.  water may 
also  collect  inside  larger  combustion-air  pipe  and  flow  to 
the burner enclosure.  failure to follow this warning could 
result  in  product  damage  or  improper  operation,  personal 
injury or death.
4.  Install  Y  concentric  fitting  and  pipe  assembly  through  
structure’s hole and field supplied roof boot/flashing.
fIGure 23.
note: do not allow insulation or other materials to accumulate 
inside pipe assembly when installing through hole.