5 - 7 
MELSEC-A
5   DATA USED FOR POSITIONING CONTROL 
 
5.1.4 Setting items for positioning data 
The "positioning data" must be set when carrying out "main positioning control". The 
setting items for the "positioning data" are shown below. 
One to 600 "positioning data" items can be set for each axis. 
Refer to "Chapter 9 MAIN POSITIONING CONTROL" for details on the "main 
positioning control", and to section "5.3 List of positioning data" for details on each 
setting item. 
 
                      Main positioning control 
 
 
 
 
 
 
Positioning data setting items 
Position control 
Speed control
 
Speed/position 
changeover control
 
Other control 
1-axis lin
ear control
 
2-axis lin
ear 
interpolation control
 
1-axis fix
ed-dimen
sion 
feed control
 
2-axis fix
ed-dimen
sion 
feed control
 
2-axis cir
cular 
interpolation control
 
C
urrent value chang
JU
MP
 comma
nd
 
Da.1
 
Operation 
pattern 
Independent 
positioning control 
 
 
 
 
 
 
 
Continuous 
positioning control 
 
 
 
 
 
 
 
Continuous path 
control 
 
 
 
 
 
 
 
Da.2
 Control method 
Linear 1 
Linear 2 
Fixed-
dimension 
feed 1 
Fixed-
dimension 
feed 2 
Circular 
interpolation
Circular 
right 
Circular left
Forward 
run 
Speed 
limited 
Reverse 
run 
Speed 
limited 
Forward run 
speed/posi-
tion 
Reverse run 
speed/posi-
tion 
Current 
value 
change 
JUMP 
command 
Da.3
 Acceleration time No. 
 
 
– – 
Da.4
 Deceleration time No. 
 
 
– – 
Da.5
 
Positioning address/movement 
amount 
 
 
 
– – 
Change 
destina-
tion 
address 
– 
Da.6
 Arc address 
– 
– 
– – – – 
Da.7
 Command speed 
 
 
– – 
Da.8
 
Dwell time/JUMP destination 
positioning data No. 
 
 
 
 
 
– 
JUMP 
destination 
positioning 
data No. 
Da.9
 M code/condition data 
 
 
 
 
 
– 
Condition 
data No. 
when 
JUMP 
 
 
 :  Always set 
 
 :  Set as required ("–" when not set) 
 
 :  Setting not possible 
 
–  :  Setting not required (This is an irrelevant item, so the setting value will be ignored. If the value is the default value or within the 
setting range, there is no problem.) 
 
*  :  The "ABS (absolute) method" or "INC (incremental) method" can be used for the control method.