Chapter 4
Block Reference
©
 National Instruments Corporation
4-9
over the Fieldbus using a host configuration tool, the block that is sending 
data to the other block is called the publisher. The block receiving the data 
is called the subscriber. When communication is established from a 
publisher to a subscriber, the subscriber takes on the value and the status of 
the published variable. If communication is not established between the 
publisher and the subscriber, the subscriber has a status that reflects the lack 
of communication. Statuses themselves are composed of three subfields: 
the quality, the substatus, and the limit.
Quality
Quality
 subfields.
Substatus
The 
Substatus
 field is used to describe more specifically the cause of the 
given quality. For example, a status with the quality of 
Bad
 might have a 
substatus of 
Device Failure
, indicating that the value should not be 
trusted because it is from a device that has failed. Another common 
substatus is 
Non-specific
. The 
Non-specific
 substatus is used when 
no other substatus applies. There are too many substatuses to explicitly list.
Table 4-3.  Quality Values
Value
Meaning
Bad
The value is bad, the sensor is defective, or 
communication has not been established. The 
value should not be trusted by the receiver.
Uncertain
The quality of the data is unknown. This can be 
caused by errors or a lack of calibration in the 
physical I/O transducer. Blocks can generally be 
configured to treat values of 
Uncertain
 quality 
as either 
Bad
 or 
Good
 with the 
STATUS_OPTS
 
parameter.
Good_NonCascade
The value is good and from a block that does not 
support cascade initialization. This status is also 
used when an alarm is active.
Good_Cascade
The value is good and from a block that supports 
cascade initialization.