Chapter 4
Block Reference
4-10
©
 National Instruments Corporation
Limit
Limit
 subfield values.
MODE_BLK Parameter and Mode Handling
The block’s mode behavior is controlled with the 
MODE_BLK
 parameter. 
The 
MODE_BLK
 parameter contains four fields that allow the current mode 
of the block to be read and the desired mode for the block to be written. The 
four fields are 
Target
 mode, 
Actual
 mode, 
Permitted
 mode, and 
Normal
 mode.
Target Mode
The desired mode of execution for the block. An operator or process 
engineer normally writes this to put the block in the desired mode of 
operation.
Table 4-4.  Limit Values
Value
Meaning
None
The value is not limited.
Low
The value is at a lower limit. This can be caused by 
a transducer limitation or setpoint limits.
High
The value is at a high limit. This can be caused by 
a transducer limitation or setpoint limits.
Constant
The value is at a fixed value and cannot move. This 
can be caused by the block supplying the value 
being in manual mode.
Table 4-5.  Target Modes
Desired Mode
Bit Set in Target Mode
Out of Service
Out of Service
, and optionally any other 
valid target mode
Manual
Manual
Automatic
Automatic
Cascade
Cascade
 and 
Automatic