Chapter 4
Block Reference
©
 National Instruments Corporation
4-11
Actual Mode
An indicator of the current mode of execution of the device. This is a 
read-only parameter. Normally, the actual mode of the block is equal to the 
target mode of the block. However, configuration errors or other conditions 
can cause it to differ from the target mode.
Remote Cascade
Remote Cascade
 and 
Automatic
. For 
more information on Remote Cascade 
operation, refer to the section 
 in Appendix D, 
.
Remote Output
Remote Output
 and 
Automatic
. For more 
information on Remote Output operation, 
refer to the section 
 in Appendix D, 
.
Table 4-6.  Actual Modes
Mode (in descending 
priority)
Meaning
Out of Service
O/S
 (0x80)
The block is idle and does not execute. If the 
resource block is out of service, all other 
blocks in the device are also out of service.
Initialization Manual
IMan
 (0x40)
The upstream block in a cascade loop is 
preparing to enter 
Auto
 mode. This mode 
cannot be set as a target mode. It is used 
internally by control blocks as they establish 
cascade loops.
Local Override
LO
 (0x20)
The block’s faultstate or interlock capability is 
causing the block to override its normal output 
value. This mode cannot be set as a target 
mode.
Manual
Man
 (0x10)
The output of the block is set by an operator 
through a write to the output parameter. No 
block processing other than writing to the 
I/O channel is performed.
Table 4-5.  Target Modes (Continued)
Desired Mode
Bit Set in Target Mode