Chapter 4
Block Reference
4-12
©
 National Instruments Corporation
Permitted Mode
A list describing the modes into which the block may be target. For 
example, in order to set a 
Target
 mode of 
Manual
, the 
Manual
 mode bit 
must be set in the 
Permitted
 mode field. The 
Permitted
 mode field also 
has an effect on the way output blocks shed modes. For a description of 
mode shedding, refer to Appendix D, 
.
Normal Mode
The block’s normal mode of operation is stored in the 
Normal
 field. This 
field is not used internally by the device, but is a guide for an operator.
Automatic
Auto
 (0x08)
The block operates normally with a setpoint 
specified manually through a write to the 
setpoint parameter.
Cascade
Cas
 (0x04)
The block operates normally with a setpoint 
specified automatically through a connection 
from an upstream block to the 
CAS_IN
 
(cascade input) parameter. Before the block 
can enter this mode, the cascade is initialized 
automatically to avoid windup.
Remote Cascade
RCas
 (0x02)
The block operates normally with a setpoint 
specified automatically through a write from a 
host computer to the 
RCAS_IN
 (remote 
cascade input) parameter. Before the block 
can enter this mode, the cascade is initialized 
automatically to avoid windup.
Remote Output
ROut
 (0x01)
The output of the block is set manually 
through a write to the 
ROUT_IN
 parameter. No 
block processing other than writing to the I/O 
channel is performed. Before the block can 
enter this mode, the cascade is initialized 
automatically to avoid windup.
Table 4-6.  Actual Modes (Continued)
Mode (in descending 
priority)
Meaning