Fig. 13
Fig. 14
Fig. 15
Cover
Address-setting
tab
FILTER
RESET
RESET
TEST
ON 
/
 OFF
Test button
ON/OFF
operation button
8.  MAINTENANCE
8-1.  Address Setting of the Remote 
Control Unit
The address can be set in order to prevent 
interference between remote controllers when two 
Sanyo indoor units are installed near each other. The 
address is normally set to "A." To set a different 
address, it is necessary to change the address on the 
second remote controller.
Once changed, you cannot restore the original 
address setting of the air conditioner.
Switching the remote controller address
(1) Open the cover on the bottom of the remote 
controller. Break the address change tab to switch 
the address to B. (Fig. 13)
(2) Insert dry cell batteries into the remote controller 
and attach the cover.
(3) Open the front panel on the stopped indoor unit, 
and use a sharp object to press the TEST button 
on the main unit controller. Verify that the indoor 
unit produces the "beep beep" signal-reception 
sound, then release the button. (Fig. 14)
(4) Next, within 5 seconds after the beep sound is 
heard from the indoor unit, press the remote con 
troller ON/OFF button and verify that the 5 beeps 
signal-reception sound occurs again. (Fig. 15) 