Section 1
General Information
Programming & Operation 4-5
MN715
Reset Parameters to Factory Settings
Sometimes it is necessary to restore the parameter values to the factory settings. Follow
this procedure to do so.
Note: All parameter values already programmed will be changed when resetting the
control to factory settings.
Action
Description
Display
Comments
Apply Power
Keypad Display shows this
opening message.
Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation.
Display mode.  Stop LED on.
Press PROG key
Enter program mode.
Press 
 or 
 key
Scroll to Level 2 Blocks.
Press ENTER key
Select Level 2 Blocks.
Press 
 or 
 key
Scroll to the Miscellaneous block.
Press ENTER key
Select Miscellaneous block.
Press 
 key
Scroll to Factory Settings
parameter.
Press ENTER key
Access Factory Settings
parameter.
 represents blinking cursor.
Press 
 key
Scroll to STD SETTINGS, to
choose original factory settings.
For 50Hz motors, set to 
50Hz/400 VOLTS.
Press ENTER key
Restores factory settings.
“Loading Presets” is first message
“Operation Done” is next
“No” is displayed last.
Press 
 key
Scroll to menu exit.
Press ENTER key
Return to Miscellaneous block.
Press DISP key
Return to display mode.
Display mode.  Stop LED on.